| 2020-02-24 11:29:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A002.2 - THERE IS AN INDICATION OF LABORATORY |
| | AND OCCUPANCY AS "B" OR BUSINESS. |
| | |
| | THIS OCCUPANCY IS MORE THAN A DENTIST OFFICE, THERE |
| | APPEARS TO BE OF MAKING AND ASSEMBLING PRODUCTS WITH |
| | ASSOCIATED OVENS. |
| | |
| | HOWEVER, PER THE FFPC 2015 ED., NFPA 101 THE OCCUPANCY |
| | SHOULD BE INDUSTRIAL. |
| | |
| | 6.1.12 INDUSTRIAL. FOR REQUIREMENTS, SEE CHAPTER 40. |
| | 6.1.12.1* DEFINITION ? INDUSTRIAL OCCUPANCY. AN |
| | OCCUPANCY IN |
| | WHICH PRODUCTS ARE MANUFACTURED OR IN WHICH PROCESSING, |
| | ASSEMBLING, |
| | MIXING, PACKAGING, FINISHING, DECORATING, OR REPAIR |
| | OPERATIONS ARE |
| | CONDUCTED. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | 2) SHEET A 120.1 - THERE ARE INDICATIONS OF A 2ND FLOOR |
| | LEVEL; HOWEVER, THERE ARE NO INDICATIONS OF WHAT THE |
| | OCCUPANCY AND PRUPOSE OF THOSE LEVELS ARE. |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAIL OF EACH AREA. |
| | |
| | |
| | |
| | 3) SHEET A 120.1 - THERE ARE INDICATIONS OF A 2ND |
| | FLOOR; HOWEVER, THERE ARE NO INDICATIONS OF WHAT THE |
| | FIRE RESISTANCE RATING OF THE SEPARATION IS. |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAIL OF EACH AREA. |
| | |
| | |
| | |
| | 4) SHEET A 120.1 - THERE ARE INDICATIONS OF A FUTURE |
| | OFFICEL; HOWEVER, THERE ARE NO INDICATIONS OF WHAT FIRE |
| | RESISTANCE RATING OF THE WALL SEPARATION IS. |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAIL OF EACH AREA. |
| | |
| | |
| | |
| | 5) SHEET A 160.1 - THERE ARE INDICATIONS OF |
| | OVENS/FURNACES; HOWEVER, THERE ARE NOMANUFACTURE |
| | SPECIFICATIONS AND VENTILATION REQUIRMENTS. |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAIL OF EACH AREA. |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |