2020-02-13 10:13:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020425
 2/13/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-102: THE ENGINEER AND ARCHITECT OF RECORD
 SHALL PROVIDE THEIR RAIDED OR INK SEALS AND WET
 SIGNATURES ON THE PLANS- FL. STATUTE 471.025 AND
 SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE & FL
 STATUTE 481.221 AND SECTION 61G-16.005 FLORIDA
 ADMINISTRATIVE CODE.
  
 2) M-102: PLEASE EXPAND ON NOTE #7 REGARDING THE
 EXHAUST SYSTEMS. PROVIDE EXHAUST VENTILATION
 CALCULATIONS AND THE SEQUENCES OF OPERATION FOR THE
 FANS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  