| 2020-02-12 10:53:22 | ROOF RECOVER BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- MAXIMUM DESIGN PRESSURES FOR SELECTED ASSEMBLY SC-95 |
| | FROM FLORIDA PRODUCT APPROVAL FL16443-R17 DOESN'T MEET |
| | THE DESIGN PRESSURE FOR ALL ROOFF ZONES. SEC. 1609.1 |
| | FBC-BUILDING. |
| | NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS |
| | (2 COPIES) AS REQUIRED BY NOTE#9 ON PAGE 2 OF 67 OF |
| | PRODUCT APPROVAL SUBMITTED. |
| | |
| | 2- NEED FIELD UPLIFT TESTING TAS 124 (2 COPIES) AS |
| | REQUIRED BY NOTE #12 ON PAGE 3 OF 67 OF FL16443-R17 |
| | FOR BONDED INSULATION OR MEMBRANE OVER EXISTING |
| | SUBSTRATES IN A RECOVER INSTALLATION. |
| | FAC 61G20-3.001SEC. 1609.1 FBC-BUILDING. |
| | |
| | 3- NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE |
| | CONTENT TEST TAS 126 (2 COPIES) AS REQUIRED BY NOTE #14 |
| | ON PAGE 3 OF 67 OF FL16443-R17 FOR RECOVER |
| | INSTALLATIONS. NOTE: THIS NOTE STATES THAT FOR RECOVER |
| | INSTALLATIONS, THE EXISTING ROOF SHALL BE EXAMINED IN |
| | ACCORDANCE WITH FBC 1521. |
| | THE REQUIRED TESTS ARE TO VERIFY THAT EXISTING ROOF IS |
| | ADEQUATE FOR RECOVER INSTALLATION. |
| | |
| | 4-THERE ARE SEVERAL BUILDINGS AND ROOF AREAS IN THIS |
| | PROPERTY. PROVIDE SKETCH (2 COPIES) SHOWING THE ROOF |
| | AREA WHERE WORK IS GOING TO TAKE PLACE. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |