2020-04-07 10:17:461) SHT. A710 - DETAIL #1 - SHOW THE DIMENSIONS OF THE
 REQUIRED CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE
 FIXTURES ON THE PLAN. COMPLY WITH 2017 FBC-ACCESS.
 SECS. 305, 604.3, 606.2.
 2) SHT. P700 - DETAIL #2 - EACH WELL OF THE THREE
 COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLY TO A
 WASTE RECEPTOR. 2017 FBC-PLUMBING SEC.802.1.1.
 3) SHT. P 110 - THE RISER SHOWS AN ICE MACHINE
 DISCHARGING TO THE GREASE WASTE SYSTEM. WASTES THAT DO
 NOT REQUIRE TREATMENT OR SEPARATION SHALL NOT BE
 DISCHARGED INTO ANY INTERCEPTOR OR SEPARATOR.
 FBC-PLUMBING SEC.1003.2.
 4) SHT. P110 - IDENTIFY FIXTURE SML ON THE RISER
 DIAGRAM ON SHT. 110. THIS IS NOT SHOWN ON THE EQUIPMENT
 SCHEDULE ON SHT. P600. - CLARIFY.
 5) SUBMIT ADDITIONAL INFORMATION ON THE INDIRECT WASTE
 FROM THE UTENSIL COUNTER. IF THIS WASTE CONTAINS ANY
 GREASE IT SHALL DISCHARGE TO THE GREASE WASTE SYSTEM.
 FBC-PLUMBING SEC.1003.1.CLARIFY.
  