| Plan Review Notes For Permit 20020408 |
| Permit Number |
20020408 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-04-07 10:17:46 | 1) SHT. A710 - DETAIL #1 - SHOW THE DIMENSIONS OF THE | | | REQUIRED CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE | | | FIXTURES ON THE PLAN. COMPLY WITH 2017 FBC-ACCESS. | | | SECS. 305, 604.3, 606.2. | | | 2) SHT. P700 - DETAIL #2 - EACH WELL OF THE THREE | | | COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLY TO A | | | WASTE RECEPTOR. 2017 FBC-PLUMBING SEC.802.1.1. | | | 3) SHT. P 110 - THE RISER SHOWS AN ICE MACHINE | | | DISCHARGING TO THE GREASE WASTE SYSTEM. WASTES THAT DO | | | NOT REQUIRE TREATMENT OR SEPARATION SHALL NOT BE | | | DISCHARGED INTO ANY INTERCEPTOR OR SEPARATOR. | | | FBC-PLUMBING SEC.1003.2. | | | 4) SHT. P110 - IDENTIFY FIXTURE SML ON THE RISER | | | DIAGRAM ON SHT. 110. THIS IS NOT SHOWN ON THE EQUIPMENT | | | SCHEDULE ON SHT. P600. - CLARIFY. | | | 5) SUBMIT ADDITIONAL INFORMATION ON THE INDIRECT WASTE | | | FROM THE UTENSIL COUNTER. IF THIS WASTE CONTAINS ANY | | | GREASE IT SHALL DISCHARGE TO THE GREASE WASTE SYSTEM. | | | FBC-PLUMBING SEC.1003.1.CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|