Plan Review Notes
Plan Review Notes For Permit 20020408
Permit Number 20020408
Review Stop M
Sequence Number 2
Notes
Date Text
2020-03-30 07:57:222ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20020408
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC AND HEATING CALCULATIONS REQUIRES THE
 ELECTRONIC SIGNATURE AND SEAL OF THE ENGINEER WHO
 PREPARED THE DOCUMENT. FL. STATUTE 471.025 AND SECTION
 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
 2) SHEET M100: PROVIDE CFM?S OF EACH SUPPLY AIR GRILL
 SUPPLIED FROM THE 20/16 DUCT FROM RTU-1 AT THE HOOD
 AREA.
 3) PLEASE INDICATE WHICH SHEET HAS THE GAS APPLIANCE
 CUT SHEETS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  