| 2020-02-27 15:41:43 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. GENERAL: ELIMINATE ALL VERBAGE ALLUDING TO EXISTING |
| | WORK. INSTEAD, REFER TO WORK PERFORMED OR TO BE |
| | PERFORMED UNDER MP 19081537. |
| | 2. PLAN PAGE SP101 INDICATES AN EXISTING 1250 GALLON |
| | GREASE TRAP. A PERMIT HAS BEEN ISSUED FOR THE GREASE |
| | TRAP AND PIPING OUT OF BUILDING INTO THE INTERCEPTOR |
| | AND CONNECTION TO THE SANITARY (SEE MASTER PERMIT |
| | 19081537 PLAN PAGE P.01 AND SUB PERMIT 20010671) |
| | ADDITIONALLY A SUB PERMIT 20011040 HAS BEEN ISSUED FOR |
| | PLUMBING FOR THE SHELL. BOTH DISCIPLINES STILL APPEAR |
| | TO BE OPEN. INDICATE ON THE NEW PLANS THAT NEW WORK IS |
| | TO BE COORDINATED WITH WORK PERMITTED UNDER MASTER |
| | PERMIT 19081537. THERE ARE INCONSISTENCIES BETWEEN MP |
| | 19081537 AND NEW MP 20020408. THE PIPING NOTED ON MP |
| | 19081537 PLAN PAGE P.01 SHALL BE INCORPORATED INTO NEW |
| | MP 20020408 AND SHALL CLEARLY INDICATE WHICH WILL BE |
| | UNDER THE OLD MP 19081537 AND WHICH IS TO BE UNDER THE |
| | NEW PERMIT. |
| | 3. PLAN SHEET P110, NOTE 7; REVISE TO READ ?TO 1250 |
| | GALLON INTERCEPTOR INSTALLED UNDER MP 19081537, SUB |
| | PERMIT 20010671. REMOVE ALL VERBAGE ALLEGING EXISTING |
| | WORK. |
| | 4. MP 19081537 PLAN SHEET P.01 INDICATES A BACKFLOW |
| | PREVENTER ON THE WATER SERVICE. NOWHERE DOES THERE |
| | APPEAR TO BE A SIZE OR LOCATION INDICATED ON THE PLANS |
| | FOR EITHER MP 19081537 OR NEW MP 20020408. PER WPB FBC |
| | 107.2.1, PROVIDE ON PLAN SHEET SP101, A LOCATION OF THE |
| | BACKFLOW PREVENTER WITH A NOTE THAT STATES A SEPARATE |
| | PERMIT SHALL BE REQUIRED FOR THE BACKFLOW PREVENTER. |
| | 5. REGARDING THE GREASE TRAP; PROVIDE CALCULATIONS TO |
| | CONFIRM THAT THE 1250 GALLON GREASE TRAP WILL BE |
| | SUFFICIENT FOR THE GREASY WASTE PER WPB FBC 107.2.1. |
| | 6. P110, NOTE 5; PROVIDE BACKFLOW PREVENTER AT ICE |
| | MACHINE PER FBC PL 608.3. |
| | 7. P110, NOTE 6; MOP SINK FAUCET SHALL BE PROVIDED WITH |
| | A VACUUM BREAKER PER FBC PL 608.2. |
| | 8. P110, NOTE 6 AND 12; CHEMICAL DISPENSER FAUCET SHALL |
| | BE PROVIDED WITH A BACKFLOW PREVENTER PER FBC PL 608.3. |
| | 9. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| | SPECIFICATION/CUT SHEETS ON ALL KITCHEN AND SPECIALTY |
| | EQUIPMENT APPURTENANCES THAT CONNECT TO WATER OR |
| | DRAINAGE, EITHER DIRECTLY OR INDIRECTLY. |
| | 10. LAVATORY TEMPERATURE LIMITING DEVICES SHALL CONFORM |
| | TO ASSE 1070 PER FBC PL 416.5. |
| | 11. THE HORIZONTAL DRY VENTS CONNECTING TO THE WATER |
| | CLOSET FIXTURE DRAINS ARE PROHIBITED PER FBC PL 905.3 |
| | (A DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE) AND 905.4 (A DRY VENT SHALL RISE VERTICALLY TO |
| | NOT LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL |
| | RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING |
| | VENTED) |
| | 12. THE HORIZONTAL DRY VENT CONNECTING TO GREASY WASTE |
| | AT THE THREE COMPARTMENT SINK IS PROHIBITED PER FBC PL |
| | 905.3 (A DRY VENT CONNECTING TO A HORIZONTAL DRAIN |
| | SHALL CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL |
| | DRAIN PIPE) AND 905.4 (A DRY VENT SHALL RISE VERTICALLY |
| | TO NOT LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD |
| | LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING |
| | VENTED) |
| | 13. PROVIDE SIZING OF THE GREASY WASTE COMPLYING WITH |
| | THE REQUIREMENTS OF FBC PL 915.2.2 AND TABLE 915.2.2. |
| | 14. PROVIDE SIZING OF THE SANITARY BUILDING DRAIN |
| | COMPLYING WITH THE REQUIREMENTS OF FBC PL 710.1 AND |
| | TABLE 710.1(1). |
| | 15. PROVIDE TRAP PRIMERS FOR FLOOR DRAINS AND TRENCH |
| | DRAINS PER FBC PL 1002.4. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 20020408 7000 OKEECHOBEE BLVD |
| | |