| 2020-02-24 15:01:27 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20010408 |
| | 2/25/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN |
| | EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, AND THE WALKIN |
| | COOLER- SECTION 107.2.1 WPB. PLEASE NOTE THAT THE COSTS |
| | ASSOCIATED WITH THESE PHASES OF THE PROJECT SHALL BE |
| | ALSO BE SEPARATED FROM THE MAIN PERMIT VALUE. PLEASE |
| | PROVIDE A COST BREAKDOWN FOR THE ENTIRE PROJECT TO |
| | VERIFY ACCURATE PERMIT VALLUE- SECTION 109.3 WPB |
| | |
| | 2) THE COMCHECK ENERGY COMPLIANCE SUBMITTAL REQUIRES |
| | THE ELECTRONIC SIGNATURE AND SEAL OF THE ENGINEER WHO |
| | PREPARED THE DOCUMENT- FL. STATUTE 471.025 AND SECTION |
| | 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | RTU'S IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 4) SHEET M600: PROVIDE MINIMUM VENTILATION CALCULATIONS |
| | FOR ALL OCCUPIED ROOMS AND SPACES- TABLE 403.3.1.1 FBC |
| | M. PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE |
| | REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 5) M600: INDICATE HOW COMBUSTION AIR IS BEING PROVIDED |
| | TO THE NEW GAS COOKING APPLIANCES AND PROVIDE |
| | CALCULATIONS- SECTION 304 FBC FG. |
| | |
| | 6) M100 & M600: AUTOMATIC SHUTOFF DAMPERS, EITHER |
| | MOTORIZED OR GRAVITY, SHALL BE PROVIDED FOR THE O/A |
| | INTAKES- SECTION C403.2.4.3 FBC-EC. |
| | |
| | 7) M700: PROVIDE DUCT HANGING AND CONNECTION DETAILS |
| | PER SMACNA STANDARDS- SECTION 603 FBC M. |
| | |
| | 8) M100: PROVIDE CONDENSATE DISPOSAL DETAILS FOR THE |
| | RTU'S- SECTION 307.2.3 FBC M. |
| | |
| | 9) M100: PROVIDE ENGINEERING FOR INSTALLATION OF THE |
| | RTU'S- SECTION 301.15 FBC M. PLEASE NOTE THAT |
| | ENGINEERING FOR THE THE KITCHEN HOOD FANS AND THE |
| | WALKIN COOLER CONDENSERS SHALL BE PROVIDED UNDER THE |
| | REQUIRED SEPARATE PERMITS. |
| | |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GAS-FIRE COOKING APPLIANCES- SECTION 623.1 FBC FG. |
| | |
| | 11) ADVISORY: THE KITCHEN HOOD IS UNDER SEPARATE |
| | PERMIT, HOWEVER PLEASE BE ADVISED THAT THE TEMPERATURE |
| | DIFFERENTIAL BETWEEN THE EXHAUST HOOD MAKEUP AIR AND |
| | THE AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 |
| | DEGREES F- SECTION 508.1.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |