| 2020-02-27 11:47:53 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | 1. PLANS INDICATE A LPG SYSTEM. PREVIOUSLY ISSUED |
| | MASTER PERMIT 19081537 FOR BUILDING SHELL DOES NOT SHOW |
| | EVIDENCE OF SEPARATE GAS PERMIT BEING APPLIED FOR AND |
| | ISSUED. CONSEQUENTLY THERE IS NO RECORD OF ANY |
| | INSTALLATION OF THAT SYSTEM AND AS SUCH THE NOTE ON NEW |
| | PERMIT 20020408 SUMITTAL (PLAN PAGE SP101) INDICATING |
| | EXISTING 1000 GALLON LP TANK IS INCORRECT. IT SHOULD |
| | READ NEW 1000 GALLON LP TANK TO BE PROVIDED UNDER A |
| | SEPARATE PERMIT. ADDITIONALLY, THE PIPING NOTED ON MP |
| | 19081537 PLAN PAGE P.01 SHALL BE INCORPORATED INTO MP |
| | 20020408 AND SHALL CLEARLY INDICATE WHICH WILL BE UNDER |
| | THE OLD MP 19081537 AND WHICH IS TO BE UNDER THE NEW |
| | PERMIT. ADDITIONALLY, THE ORIGINAL MP DRAWINGS DO NOT |
| | PROVIDE FOR LONGEST LENGTH AND LOAD FOR THE 2 PSI |
| | PIPING AND CALCULATIONS SHALL BE PROVIDED FOR THE SAME. |
| | IF THE STEPDOWN REGULATOR IS IN MP 20020408 SCOPE OF |
| | WORK, THEN PROVIDE A DETAIL SHOWING REGULATOR WITH |
| | SHUTOFF VALVE, UNION AND DIRT LEG. PROVIDE |
| | MANUFACTURE'S SPECIFICATION; REGULATOR SHALL BE RATED |
| | FOR OUTDOORS. ALL VERBAGE ALLUDING TO EXISTING SHALL BE |
| | REMOVED AND INSTEAD SHALL REFERENCE WORK PROVIDED UNDER |
| | MP 19081537. |
| | 2. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE |
| | BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR. FBC FG |
| | 304.9.3 |
| | 3. PER WPB FBC 107.2.1 SUBMIT MANUFACTURER'S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT INCLUDING BUT NOT LIMITED TO KITCHEN, WATER |
| | HEATER AND ROOFTOP AIR CONDITIONING UNITS. TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG |
| | 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND |
| | LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | 4. PLAN SHEET A131: KES 13 (GRILL) AND KES 14 (RANGE) |
| | INDICATE NATURAL GAS AS FUEL; PLAN SHEET P100 INDICATES |
| | FUEL TYPE IS LP. PER WPB FBC 107.2.1, RECONCILE THE TWO |
| | PLAN SHEETS. |
| | 5. PLAN SHEET P100; GAS RISER NOTES A SECTION OF |
| | HORIZONTAL PIPING DOWNSTREAM OF DWH-1 CONNECTION SIZED |
| | 1 INCH. SHALL BE 1-1/4 INCH PER FBC FG TABLE 402.4(28). |
| | 6. SUBMIT A COMPLETE DETAIL SHOWING THE TYPE, LOCATION, |
| | SIZE, TERMINATION POINT, HEIGHT ABOVE THE FINISH ROOF |
| | AND ANCHORING DETAILS OF THE GAS VENT(S) PER FBC FG 502 |
| | THRU 505 |
| | 7. REVISE DETAIL SHOWING THE EMERGENCY HOOD SHUT DOWN |
| | SHUT OFF VALVE. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE |
| | SHALL BE BELOW THE CEILING. THE MANUAL SHUTOFF VALVE |
| | SHALL BE UPSTREAM. "UNION TO BE DOWN STREAM OF MANUAL |
| | VALVE". SECS. 10.4, 10.5 OF NFPA 96-08. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 20020408 7000 OKEECHOBEE BLVD |