| Date |
Text |
| 2020-03-02 11:14:55 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) VALUE IS LOW FOR THIS TYPE OF BUILDOUT. $200,000 |
| | |
| | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 2) PAGE E110 |
| | A FEW NOTES CALL FOR " BY OWNER" THIS NEEDS TO BE |
| | INCLUDED IN THE VALUE OF THE PERMIT. |
| | KITCHEN AND KITCHEN AREA SEEMS TO BE MISSING GFCI |
| | PROTECTION ON 15 AND 20 AMPR RECEPTACLES. |
| | 210.8 (B) OTHER THAN DWELLING UNITS. ALL 125-VOLT, |
| | SINGLE-PHASE, |
| | 15- AND 20-AMPERE RECEPTACLES INSTA LLED IN THE |
| | LOCATIONS SPECIFIED |
| | IN 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| | CIRCUITINTERRUPTER |
| | PROTECTION FOR PERSONNEL. (2) KITCHENS (5) SINKS ? |
| | WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT) |
| | OF THE OUTSIDE EDGE OF THE SINK, |
| | |
| | 3) NO PANEL SCHEDULES ARE INCLUDED WITH PLANS. |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY |
| | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO |
| | ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE |
| | IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF |
| | DETAIL THAT ALLOWS |
| | EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE |
| | POSITIONS THAT CONTAIN UNUSED OVERCURRENT DEVICES OR |
| | SWITCHES SHALL BE |
| | DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE |
| | INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE |
| | FACE OR INSIDE OF THE |
| | PANEL DOOR IN THE CASE OF A PANELBOARD AND AT EACH |
| | SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD OR |
| | SWITCHGEAR |
| | |
| | 4) NO LOAD CALCULATION INCLUDED WITH THE PLANS. |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220 |
| | |
| | 5) NO FAULT CURRENT CALCULATION FOR AIC RATING INCLUDED |
| | WITH THE PLANS. |
| | PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT |
| | AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC |
| | 110.10 |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED |
| | WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24 |
| | PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | |
| | 6) PAGE E710 |
| | SEPARATE PERMIT REQUIRED FOR UPS SYTEM BY OWNER. |