Plan Review Notes
Plan Review Notes For Permit 20020408
Permit Number 20020408
Review Stop E
Sequence Number 1
Notes
Date Text
2020-03-02 11:14:55FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE IS LOW FOR THIS TYPE OF BUILDOUT. $200,000
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) PAGE E110
 A FEW NOTES CALL FOR " BY OWNER" THIS NEEDS TO BE
 INCLUDED IN THE VALUE OF THE PERMIT.
 KITCHEN AND KITCHEN AREA SEEMS TO BE MISSING GFCI
 PROTECTION ON 15 AND 20 AMPR RECEPTACLES.
 210.8 (B) OTHER THAN DWELLING UNITS. ALL 125-VOLT,
 SINGLE-PHASE,
 15- AND 20-AMPERE RECEPTACLES INSTA LLED IN THE
 LOCATIONS SPECIFIED
 IN 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUITINTERRUPTER
 PROTECTION FOR PERSONNEL. (2) KITCHENS (5) SINKS ?
 WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT)
 OF THE OUTSIDE EDGE OF THE SINK,
  
 3) NO PANEL SCHEDULES ARE INCLUDED WITH PLANS.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE
 IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF
 DETAIL THAT ALLOWS
 EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE
 POSITIONS THAT CONTAIN UNUSED OVERCURRENT DEVICES OR
 SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE
 FACE OR INSIDE OF THE
 PANEL DOOR IN THE CASE OF A PANELBOARD AND AT EACH
 SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD OR
 SWITCHGEAR
  
 4) NO LOAD CALCULATION INCLUDED WITH THE PLANS.
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220
  
 5) NO FAULT CURRENT CALCULATION FOR AIC RATING INCLUDED
 WITH THE PLANS.
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24
 PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 6) PAGE E710
 SEPARATE PERMIT REQUIRED FOR UPS SYTEM BY OWNER.