| 2020-03-02 10:57:58 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20020396 |
| | ADD: 4510 GARDEN AVE. |
| | CONT: UNIVERSAL WORLD CONSTRUCTION |
| | TEL: 954-317-6771 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY, MARCH 02/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE RATIONAL ANALYSIS AND ENGINEERING DESIGN |
| | CALCULATIONS SUBMITTED HAS A COVERSHEET AND 5 NUMBERED |
| | PAGES. THE NUMBER PAGE ONE IS THE ONLY SHEET THAT IS |
| | SIGNED AND SEALED BY THE ENGINEER OF RECORD. |
| | |
| | FLORIDA ADMINISTRATIVE CODE. 61G15-23.002(2)(B) FL. |
| | ADMIN. CODE. A COVER SHEET WITH LISTED PAGES OR INDEX |
| | SHEET FOR ENGINEERING CALCULATIONS AND OR |
| | SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE |
| | SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & |
| | PREPARATION OF EACH SECTION OF THE ENGINEERING |
| | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| | SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER |
| | THE COVER SHEET OR INDEX SHEET. |
| | |
| | 2) SHEET 1 OF THE CALCULATIONS INDICATES THE COLUMN |
| | HEIGHT OF 5 FEET WHEREAS THE PLANS SHEET DT1 DETAIL # 8 |
| | INDICATES THE COLUMN TO BE 6 FEET 4 INCHES TALL? |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | DISCREPANCY BETWEEN THE PLAN AND CALCULATIONS. |
| | |
| | 3) SHEET 1 OF THE CALCULATIONS INDICATES THE BASIC WIND |
| | VELOCITY OF 170 MPH AND WIND DESIGN OF 115 MPH. |
| | THE BASIC WIND VELOCITY OF 170 MPH SHOULD IT NOT READ, |
| | 170 MPH VULT THIS WOULD BE FOR CATEGORY II STRUCTURES, |
| | THE DERATING TO VASD WOULD THEN BE 132 MPH VASD SEE |
| | FIGURE 1609.3(1). FOR STRUCTURES IN A CATEGORY I |
| | CLASSIFICATION THE WIND DESIGN WOULD BE 150 MPH VULT |
| | AND 116 MPH VASD NOT 115 VULT. PLEASE PROVIDE |
| | ADDITIONAL INFORMATION 107.2.1.2. |
| | |
| | 4) THE SITE PLAN DOES NOT PROVIDE TO WHAT SCALE THE |
| | PLANS WERE DRAWN, THEY INDICATE NOT TO SCALE. THE PLAN |
| | ALSO INDICATES THE POST FOR THE WALL SYSTEM AND |
| | FOUNDATIONS. THERE ARE FOUNDATIONS ON THE WEST, NORTH |
| | AND EAST SIDE OF THE PROPERTY THAT EXTEND PAST THE |
| | PROPERTY LINE AND INTO THE RIGHT OF WAY. THE 2017 FBC-B |
| | DOES NOT ALLOW FOR FOUNDATIONS PAST THE PROPERTY LINE |
| | SEE FBC-B 3202.1.1. PLEASE ADJUST THE PLANS FOR ALL |
| | FOUNDATIONS TO BE WITHIN THE PROPERTY LINE. |
| | |
| | 5) PLEASE PROVIDE A CURRENT SURVEY LESS THAN A YEAR |
| | OLD. 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION |
| | 107.3.5.3. MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |