| Plan Review Notes For Permit 20020383 |
| Permit Number |
20020383 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-06-12 12:46:20 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT-20020383 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET E-01 SHOWS A WALL RUNNING ALL THE WAY ACROSS | | | THE BACK OF THE ROOM CREATING A SMALL ROOM BEHIND. THE | | | CCU-01 IS LOCATED INSIDE THIS ROOM. WHAT IS THIS ROOM? | | | SHEET M-00 DOES NOT SHOW A RETURN DUCT WHICH WOULD MEAN | | | THE RETURN IS COMING FROM THE MYSTERY ROOM. IS THIS | | | ROOM CONDITIONED? PLEASE LABEL THIS ROOM AND SHOW THE | | | RETURN PATH TO THE CCU-01. PLEASE BE CONSISTENT BETWEEN | | | DRAWINGS. FBC FS 107.2.1 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|