2020-06-12 12:46:202ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20020383
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-01 SHOWS A WALL RUNNING ALL THE WAY ACROSS
 THE BACK OF THE ROOM CREATING A SMALL ROOM BEHIND. THE
 CCU-01 IS LOCATED INSIDE THIS ROOM. WHAT IS THIS ROOM?
 SHEET M-00 DOES NOT SHOW A RETURN DUCT WHICH WOULD MEAN
 THE RETURN IS COMING FROM THE MYSTERY ROOM. IS THIS
 ROOM CONDITIONED? PLEASE LABEL THIS ROOM AND SHOW THE
 RETURN PATH TO THE CCU-01. PLEASE BE CONSISTENT BETWEEN
 DRAWINGS. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  