Plan Review Notes
Plan Review Notes For Permit 20020383
Permit Number 20020383
Review Stop E
Sequence Number 2
Notes
Date Text
2020-06-19 09:23:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2 (SEE SIGNATURE COMMENTS.
 ALTHOUGH THE EXEMPTION APPLIES AND AN ARCHITECT OR
 ENGINEER IS NOT REQUIRED FOR THE PLANS, SOMEONE HAS TO
 TAKE RESPONSIBILITY AND SIGN EACH SHEET OF THE PLAN,
 THIS IS THE PERSON DESIGNING THE PLAN AS THE
 RESPONSIBLE PERSON. IF AN ARCHITECT OR ENGINEERING FIRM
 BLOCK STAMP IS ON THE PLAN, THEN IT MUST BE
 SIGNED/SEALED PER FLORIDA STATUTES.)
 2. PLAN SHOWS A TYPICAL RISER DIAGRAM. PROVIDE THE
 ACTUAL RISER DIAGRAM OF THE EXISTING SERVICE. SHOW ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1 (RISER DIAGRAM QUOTES THE 2008
 NEC AS THE BASIS FOR DESIGN. THIS IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. SEE CURRENT CODES ABOVE.)
 3. CORRECTED, SEE NEW COMMENT BELOW.
 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2 (LOAD CALCULATION IS NOT CODE COMPLIANT. SEE
 FBC 3602 FOR METHOD OF CALCULATION REQUIRED.)
 5. CORRECTED.
  
 NEW COMMENTS:
  
 6. PANEL SCHEDULE SHOWS A 100 AMP PANEL WITH 164 AMPS
 LOAD. RISER DIAGRAM ONLY SHOWS ONE 200 AMP PANEL, IS
 THERE ANOTHER PANEL? WHY IS THIS PANEL LABELED UNIT 3?
 PROVIDE CLARIFICATIONS AND/OR CORRECTIONS AS NEEDED.
 NEC 215.5, 230, 250.50, 250.94, 408.30; FBC RE E3706.1,
 E3608.1, E3609.3; WPB FBC 107.2.1
 7. PLAN SHOWS A NEW TANKLESS WATER HEATER WITH A LOAD
 OF 18,000 VA SUPPLIED BY #8 WIRE ON A 40 AMP BREAKER. A
 LOAD OF 18,000 VA WOULD DRAW 75 AMPS. PROVIDE CORRECTED
 WIRING AND OVERCURRENT PROTECTION FOR THIS WATER
 HEATER. NEC 240.4, 310.15(B)(16); FBC RE E3705.1
 8. ELECTRICAL PLAN DOES NOT SHOW THE NEW MINI-SPLIT
 A/C. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 9. PLAN SHOWS A 15 AMP CIRCUIT FEEDING TWO NEW
 BATHROOMS. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 10. NOTE 19 REFERS TO THE 2011 NEC FOR AFCI
 REQUIREMENTS. THIS IS NOT THE CURRENT CODE AND THE
 REQUIREMENTS HAVE CHANGED. ALL BRANCH CIRCUITS THAT
 SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 11. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION OR NOTE
 FOR COMPLIANCE. NEC 410.10(D); FBC RE E4003.11
 12. NOTE 20 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11 FROM THE 2011 NEC. THIS IS NOT
 THE CURRENT CODE AND THIS CODE SECTION DOES NOT APPLY
 TO TAMPER RESISTANT RECEPTACLES. PROVIDE CORRECTION.
 NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  