Plan Review Notes
Plan Review Notes For Permit 20020383
Permit Number 20020383
Review Stop P
Sequence Number 1
Notes
Date Text
2020-03-02 15:56:1403/02/2020 PLUMBING 1ST REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
  
 2. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ELECTRIC WATER HEATER
 EQUIPMENT TO VERIFY COMPLIANCE PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. THE SECOND BATHROOM DOWN STREAM NEED TO BE ON A
 SEPARATE SYSTEM ON A BRANCH I HAVE NOTED ON ONE OF THE
 PLANS THE CORRECT WAY SO YOU CAN HAND WRITE IN THE
 SECOND SET OF PLANS PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THERE ARE SHOWERS ON THE ISOMETRIC AND TUB ON THE
 FLAT, IF YOU ARE PUTTING SHOWERS PLEASE A DETAIL
 CONFORMING WITH 2017 FBC SECTION R2709.2 AND IS
 RECESSED IN CONCRETE PLEASE NOTE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  