2020-03-10 17:35:10PERMIT # 20020383
  
 MECHANICAL REVIEW
  
 CODES IN EFFECT:
  
 2017 EDITIONS OF:
 FBC RE = FLORIDA RESIDENTIAL CODE, 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION, 6TH
 EDITION
  
 MICHAEL EDWARDS
 MECHANICAL PLANS EXAMINER II
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6728
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
  
 1) PLEASE PROVIDE CALCULATIONS FROM ACCA MANUAL S, J
 AND D.
  
 FBC CHAPTER 1 ADMINISTRATION- 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS -107.3.5.1.4 MECHANICAL;
 ALSO SEE FBC CE SECTION R403.7 PLEASE PROVIDE
 CALCULATIONS FROM ACCA MANUAL J.
  
 2) PROVIDE THE SPEC SHEETS FOR THE MITSUBISHI
 PUZ-A12NKA7.
  
 FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
 3) PLEASE SHOW THE RETURN AIR PATH BACK TO THE CCU-01
 UNIT. RETURN AIR MUST NOT BE TAKEN FROM A CLOSET.
  
 M1602.2 RETURN AIR OPENINGS. (4) RETURN AIR SHALL NOT
 BE TAKEN FROM A CLOSET, BATHROOM, TOILET ROOM, KITCHEN,
 GARAGE, MECHANICAL ROOM, BOILER ROOM, FURNACE ROOM OR
 UNCONDITIONED ATTIC.
  
 4) PROVIDE DUCT SIZE FOR DUCT AT AIR DEVICE A-3.
  
 FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
 5) MECHANICAL DRAWINGS MUST BE SIGNED BY DESIGNER.
  
 1) . FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 6) PLEASE PROVIDE SPEC SHEETS FOR THE HOOD AND THE
 APPLIANCE GOING UNDER THIS HOOD THAT IS LOCATED ON THE
 PORCH.
  
 . FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 7) PLEASE SHOW THE AUXILIARY OR SECONDARY CONDENSATE
 DRAINAGE SYSTEM FOR THE CCU-01.
  
 M1411.3.1AUXILIARY AND SECONDARY DRAIN SYSTEMS.
 IN ADDITION TO THE REQUIREMENTS OF SECTION M1411.3, A
 SECONDARY DRAIN OR AUXILIARY DRAIN PAN SHALL BE
 REQUIRED FOR EACH COOLING OR EVAPORATOR COIL WHERE
 DAMAGE TO ANY BUILDING COMPONENTS WILL OCCUR AS A
 RESULT OF OVERFLOW FROM THE EQUIPMENT DRAIN PAN OR
 STOPPAGE IN THE CONDENSATE DRAIN PIPING. SUCH PIPING
 SHALL MAINTAIN A MINIMUM HORIZONTAL SLOPE IN THE
 DIRECTION OF DISCHARGE OF NOT LESS THAN 1/8 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (1-PERCENT SLOPE).
 DRAIN PIPING SHALL BE NOT LESS THAN 3/4-INCH (19 MM)
 NOMINAL PIPE SIZE. ONE OF THE FOLLOWING METHODS SHALL
 BE USED:
 1. 1.AN AUXILIARY DRAIN PAN WITH A SEPARATE DRAIN SHALL
 BE INSTALLED UNDER THE COILS ON WHICH CONDENSATION WILL
 OCCUR. THE AUXILIARY PAN DRAIN SHALL DISCHARGE TO A
 CONSPICUOUS POINT OF DISPOSAL TO ALERT OCCUPANTS IN THE
 EVENT OF A STOPPAGE OF THE PRIMARY DRAIN. THE PAN SHALL
 HAVE A MINIMUM DEPTH OF 1.5 INCHES (38 MM), SHALL BE
 NOT LESS THAN 3 INCHES (76 MM) LARGER THAN THE UNIT OR
 THE COIL DIMENSIONS IN WIDTH AND LENGTH AND SHALL BE
 CONSTRUCTED OF CORROSION-RESISTANT MATERIAL. GALVANIZED
 SHEET STEEL PANS SHALL HAVE A MINIMUM THICKNESS OF NOT
 LESS THAN 0.0236-INCH (0.6010 MM) (NO. 24 GAGE).
 NONMETALLIC PANS SHALL HAVE A MINIMUM THICKNESS OF NOT
 LESS THAN 0.0625 INCH (1.6 MM).
 2. 2.A SEPARATE OVERFLOW DRAIN LINE SHALL BE CONNECTED
 TO THE DRAIN PAN INSTALLED WITH THE EQUIPMENT. THIS
 OVERFLOW DRAIN SHALL DISCHARGE TO A CONSPICUOUS POINT
 OF DISPOSAL TO ALERT OCCUPANTS IN THE EVENT OF A
 STOPPAGE OF THE PRIMARY DRAIN. THE OVERFLOW DRAIN LINE
 SHALL CONNECT TO THE DRAIN PAN AT A HIGHER LEVEL THAN
 THE PRIMARY DRAIN CONNECTION.
 3. 3.AN AUXILIARY DRAIN PAN WITHOUT A SEPARATE DRAIN
 LINE SHALL BE INSTALLED UNDER THE COILS ON WHICH
 CONDENSATION WILL OCCUR. THIS PAN SHALL BE EQUIPPED
 WITH A WATER LEVEL DETECTION DEVICE CONFORMING TO UL
 508 THAT WILL SHUT OFF THE EQUIPMENT SERVED PRIOR TO
 OVERFLOW OF THE PAN. THE PAN SHALL BE EQUIPPED WITH A
 FITTING TO ALLOW FOR DRAINAGE. THE AUXILIARY DRAIN PAN
 SHALL BE CONSTRUCTED IN ACCORDANCE WITH ITEM 1 OF THIS
 SECTION.
 4. 4.A WATER LEVEL DETECTION DEVICE CONFORMING TO UL
 508 SHALL BE INSTALLED THAT WILL SHUT OFF THE EQUIPMENT
 SERVED IN THE EVENT THAT THE PRIMARY DRAIN IS BLOCKED.
 THE DEVICE SHALL BE INSTALLED IN THE PRIMARY DRAIN
 LINE, THE OVERFLOW DRAIN LINE OR THE EQUIPMENT-SUPPLIED
 DRAIN PAN, LOCATED AT A POINT HIGHER THAN THE PRIMARY
 DRAIN LINE CONNECTION AND BELOW THE OVERFLOW RIM OF
 SUCH PAN.
 M1411.3.1.1WATER-LEVEL MONITORING DEVICES.
 ON DOWN-FLOW UNITS AND OTHER COILS THAT DO NOT HAVE
 SECONDARY DRAIN OR PROVISIONS TO INSTALL A SECONDARY OR
 AUXILIARY DRAIN PAN, A WATER-LEVEL MONITORING DEVICE
 SHALL BE INSTALLED INSIDE THE PRIMARY DRAIN PAN. THIS
 DEVICE SHALL SHUT OFF THE EQUIPMENT SERVED IN THE EVENT
 THAT THE PRIMARY DRAIN BECOMES RESTRICTED. DEVICES
 SHALL NOT BE INSTALLED IN THE DRAIN LINE.
  
 8) PLEASE PROVIDE AN ENGINEER?S SEAL AND SIGNATURE ON
 THE CONDENSER MOUNTING DETAIN DESIGN.
  
 . FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved