| 2020-02-25 12:31:14 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. PLAN SHEET A-1 IN LAB ROOM 114 THERE IS A DETAIL |
| | 2/A-2. THE LAB SINK IS AT 36 INCHES IN HEIGHT. PLEASE |
| | REVIEW THE 2017 FBC-ACCESSIBILITY CODE CHARGING SECTION |
| | 212.3. SINKS. WHERE SINKS ARE PROVIDED, AT LEAST 5 |
| | PERCENT, BUT NOT FEWER THAN ONE, OF EACH TYPE PROVIDED |
| | IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606. |
| | THIS ALSO APPLIES TO ROOMS 107, 108 AND 110. ONE OF THE |
| | THREE ROOMS SHALL COMPLY. SHOW CLEAR FLOOR SPACES FOR |
| | EACH ACCESSIBLE SINK. THE CLEAR FLOOR OR GROUND SPACE |
| | SHALL BE 30 INCHES (760 MM) MINIMUM BY 48 INCHES (1220 |
| | MM) MINIMUM AND COMPLY WITH FBC ACC SECTION 305. THE |
| | ACCESSIBLE SINKS SHALL BE INSTALLED WITH THE FRONT OF |
| | THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC |
| | 606.3, |
| | 2. PLAN SHEET A-1 INDICATES THERE WILL BE AN EXCHANGE |
| | OF DRINKING FOUNTAINS A SINGLE FOUNTAIN FOR A HIGH/ LOW |
| | ADA DRINKING FOUNTAIN. PER WPB FBC 107.2.1, PROVIDE A |
| | DETAIL SHOWING COMPLIANCE WITH FBC ACC 307.2. |
| | 3. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| | SPECIFICATIONS FOR THE TANKLESS WATER HEATER. PROVIDE |
| | CALCULATIONS FOR HOT WATER DEMAND PLACED ON WATER |
| | HEATER AND SHOW THAT THE WATER HEATER HAS THE CAPACITY |
| | TO MEET THE DEMAND. REFER TO FBC PL TABLE 404.3 FOR |
| | WATER SYSTEM DEMAND FOR THE FIXTURE. |
| | 4. PER WPB FBC 107.2.1, ADD TO THE PLUMBING FIXTURE |
| | SCHEDE THE HIGH/LOW BARRIER FREE DRINKING FOUNTAIN |
| | NOTED ON PLAN SHEET A-1 |
| | 5. PER WPB FBC 107.2.1, PROVIDE SPECIFIC SPECIFICATION |
| | FOR SUMP DISCHARGE PIPE, VALVES AND FITTINGS. PIPE AND |
| | FITTINGS SHALL COMPLY WITH FBC PL 712.3.3, 712.3.3.1 |
| | AND 712.3.3.2. |
| | 6. PER FBC PL 712.2, PROVIDE A FULL OPEN VALVE ON THE |
| | DISCHARGE SIDE OF THE CHECK VALVE. |
| | 7. PER WPB FBC 107.2.1, PROVIDE A NOTE AT THE POINT |
| | WHERE THE SUMP PUMPS DISCHARGE ENTERS THE BUILDING |
| | DRAIN STATING "DISCHARGE LINE SHALL CONNECT TO BUILDING |
| | DRAIN THROUGH A WYE INTO THE TOP OF THE DRAINAGE |
| | PIPING; SUCH WYE SHALL BE NOT LESS THAN TEN (10) PIPE |
| | DIAMETERS DOWNSTREAM OF THE WATER CLOSET CONNECTION AS |
| | REQUIRED BY FBC PL 712.3.5." |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |