| 2020-02-20 10:02:02 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20020370 |
| | 2/20/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1: REFER TO THE BUILDING REVIEW COMMENTS. |
| | THERE ARE MISSING ARCHITECTURAL AND LIFE SAFETY PLAN |
| | DETAILS THAT WILL EFFECT THE NEW AC DUCT PLANS. BASED |
| | ON THE CURRENT PLANS AND THE COMMENTS IT APPEARS THAT |
| | FIRE DAMPERS ARE MSSING FROM THE DUCT PENETRATIONS AT |
| | THE FIRE-RATED STAIRWELL WALLS, AND FOR ALL ALL THE |
| | SUPPLY DIFFUSER PENETRATIONS OF THE FIRE-RATED |
| | FLOOR/CEILING ASSEMBLY- SEE SECTION 607.5.2 & 607.6.1. |
| | IT WOULD BE HELPFUL TO PROVIDE A REFLECTIVE CEILING |
| | PLAN AND A BUILDING SECTION CUT TO CLARIFY HIOW THE |
| | DUCTS WILL BE RUN THROUGHOUT THE FIRST FLOOR- SECTION |
| | 107.2.1 WPB. |
| | |
| | 2) M1: CLARIFY HOW AIR IS BEING RETURNED TO AHU-2- |
| | SECTION 601.6 FBC M. THERE DOESN'T APPEAR TO BE A MAIN |
| | RETURN GRILL IN THE STAIRWELL WALL OR DOOR. PLEASE NOTE |
| | THAT ANY OPENINGS IN THE WALL OR DOOR WOULD REQUIRE |
| | FIRE DAMPERS- SECTION 607.5.2. |
| | |
| | 3) M1: THE PLAN SHOWS A NEW LAB WHICH MAY REQUIRE A |
| | DEDICATED EXHAUST VENTILATION SYSTEM. PLEASE SEE |
| | SECTION 510.1 FBC M AND PROVIDE A BRIEF NARREATIVE ON |
| | THE PLAN DESCRIBING THE WORK THAT WILL BE PERFORMED IN |
| | THE LAB, AND MATERIALS THAT WILL BE PROCESS AND/OR |
| | STORED THERE. FOR THE PURPOSES OF THE PROVISIONS OF |
| | SECTION 510, A LABORATORY SHALL BE DEFINED AS A |
| | FACILITY WHERE THE USE OF CHEMICALS IS RELATED TO |
| | TESTING, ANALYSIS, TEACHING, RESEARCH OR DEVELOPMENTAL |
| | ACTIVITIES. CHEMICALS ARE USED OR SYNTHESIZED ON A |
| | NONPRODUCTION BASIS, RATHER THAN IN A MANUFACTURING |
| | PROCESS. |
| | |
| | 4) SHOW THE LOCATION OF THE NEW CONDENSER ON THE ROOF. |
| | PLEASE REFER TO BUILDING REVIEW COMMENT #13 ABOUT THE |
| | AC STAND AND SHOW COMPLIANCE. |
| | |
| | 5) THE AC CALCULATIONS ARE LISTING THE PROJECT LOCATION |
| | AS PALM BEACH GARDENS- PLEASE CORRECT- SECTION C403.2.1 |
| | FBC M. |
| | |
| | 6) PROVIDE A PRODUCT DATA SUBMITTAL FOR THE MOTORIZED |
| | DAMPERS WITH REVIEW AND APPROVAL STAMP BY THE EOR- |
| | SECTION 107.2.1 WPB & SECTION C403.2.4.3 FBC EC. PLEASE |
| | NOTE THE SUBMITTAL MAY BE DEFERRED PER SECTION |
| | 107.3.4.2 WPB. |
| | |
| | 7) M1: ACCESS PANELS SHALL BE PROVIDED FOR THE |
| | MOTORIZED DAMPERS IF TO BE LOCATED ABOVE A DRYWALL |
| | CEILING- SECTION 306.1 FBC M. |
| | |
| | 8) M1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR |
| | HANDLERS- SECTION 307.2.3 FBC M. PLEASE NOTE THAT |
| | COMNDESNATE SHALL NOT BE DISCHARGED INTO THE CITY |
| | ANITARY SYSTEM- SECTIOB |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |