| 2020-03-09 10:43:39 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NEW PANEL A IS SHOWN AS A 100 AMP PANEL FED WITH #3 |
| | WIRE. THE LOAD ON THIS PANEL IS SHOWN AS 132 AMPS. THE |
| | PANEL AND THE WIRE FEEDING IT ARE UNDERSIZED FOR THIS |
| | LOAD. PROVIDE CORRECTION. NEC 215.2, 310.15, 408.30 |
| | 2. NEW PANEL C IS SHOWN AS A 100 AMP PANEL FED WITH #3 |
| | WIRE. THE LOAD ON THIS PANEL FOR B PHASE IS SHOWN AS |
| | 143 AMPS. THE PANEL AND THE WIRE FEEDING IT ARE |
| | UNDERSIZED FOR THIS LOAD. PROVIDE CORRECTION. NEC |
| | 215.2, 310.15, 408.30 |
| | 3. LOAD FOR PANEL LP1 DOES NOT APPEAR TO INCLUDE THE |
| | LOAD FOR PANEL LP2, WHICH IS SHOWN AS BEING FED FROM |
| | PANEL LP1. PROVIDE CLARIFICATION AND/OR CORRECTIONS. |
| | NEC 215.2, 310.15, 408.30 |
| | 4. THE EXISTING SERVICE DISCONNECT IS SHOWN AS A 400 |
| | AMP SERVICE. THE LOAD PROPOSED WOULD EXCEED THE |
| | CAPACITY OF THIS SERVICE. PROVIDE CORRECTION. NEC |
| | 215.2, 310.15, 408.30 |
| | 5. SPECIFY WIRE SIZE OF EXISTING FEEDERS TO CONFIRM |
| | CODE COMPLIANCE. WPB FBC 107.2.1; NEC 215.2, 310.15 |
| | 6. INDICATE ON PLAN WHICH AREAS ARE TO BE WIRED PER NEC |
| | 517.13. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |