| 2020-04-07 14:34:06 | REVIEW BY JERRY SMITH: |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20020362 591 EVERNIA ST |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | PLEASE SEE MARKED UP PLAN SHEETS A3.1, P001 AND P601. |
| | 1. SHEET A3.1: PROVIDE NOTE; ?MEN?S BATHROOM ELEV. RM. |
| | #108-SIMILAR TO WOMEN?S BATHROOM ELEV. RM. #109 |
| | ENLARGED DETAILS? |
| | 2. REGARDING ADA CTLS/SH-2: PLAN SHEET A301 INDICATES |
| | TWO CONTROL VALVES. WHAT IS THE PURPOSE OF THE CONTROL |
| | VALVE ADJACENT TO THE EMTRANCE? ADDITIONALLY, HOW IS |
| | THE ADA CONTROL VALVE ON THE SIDE WALL PLUMBED? PLAN |
| | SHEET P601 WATER RISER DOES NOT ADDRESS. PER WPB FBC |
| | 107.2.1, CLARIFY. ADDITIONALLY, FIXTURE SCHEDULE ON |
| | P001 DOES NOT ADDRESS. AGAIN, CLARIFY. |
| | 3. PROVIDE NOTE; PER FBC ACC 608.5.3, IN ALTERNATE |
| | ROLL-IN TYPE SHOWER COMPARTMENTS, THE CONTROLS, |
| | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE LOCATED ABOVE |
| | THE GRAB BAR, BUT NO HIGHER THAN 48 INCHES (1220 MM) |
| | ABOVE THE SHOWER FLOOR. WHERE A SEAT IS PROVIDED, THE |
| | CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE |
| | LOCATED ON THE SIDE WALL ADJACENT TO THE SEAT 27 INCHES |
| | (685 MM) MAXIMUM FROM THE SIDE WALL BEHIND THE SEAT OR |
| | SHALL BE LOCATED ON THE BACK WALL OPPOSITE THE SEAT 15 |
| | INCHES (380 MM) MAXIMUM, LEFT OR RIGHT, OF THE |
| | CENTERLINE OF THE SEAT. WHERE A SEAT IS NOT PROVIDED, |
| | THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE |
| | INSTALLED ON THE SIDE WALL FARTHEST FROM THE |
| | COMPARTMENT ENTRY. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |