Plan Review Notes
Plan Review Notes For Permit 20020362
Permit Number 20020362
Review Stop M
Sequence Number 2
Notes
Date Text
2020-04-08 11:46:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020362
 4/8/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC COOLING AND HEATING CALCULATIONS FOR AHU-1-1
 ARE INDICATING MIAMI AS THE PROJECT LOCATION. PLEASE
 CLARIFY WHY THE COOLING LOADS ARE BEING DETERMINED IN
 NOVEMBER AND THE HEATING LOADS IN MAY. WHY WOULDN'T
 THESE LOADS BE CALCULATED DURING PEAK TIMES- SECTION
 C403.2.1 FBC EC.
  
 2) SHEET M001: NO CHANGES WERE MADE TO THE DESIGN
 CONDITIONS INFO ON M0001. THE 1ST REVIEW COMMENT
 REMAINS- DESIGN CONDITIONS LISTED ARE INCORRECT. A)
 WEST PALM BEACH SUMMER OUTDOOR DRY BULB IS 91, WINTER
 DRY BULB IS 45. B) OCCUPIED HEATING- 72. REFER TO TABLE
 D101 FBC- 2017 PLUMBING WHICH IS BASED ON ASHRAE 183.
 .
 6) M802: THE NARRATIVE RESPONSE REFERENCES STRUCTURAL
 DRAIWNGS FOR RTU INSTALLATION DETAILS, HOWEVER NONE ARE
 PROVIDED. THE 1ST REVIEW COMMENTS REMANINS- PROVIDE
 ENGINEERED DETAILS FOR ANCHORING THE NEW CONDENSERS-
 SECTION 301.15 FBC M. PLEASE NOTE THAT ENGINEERING AND
 ITEMS LISTED BELOW MAY BE DEFERRED SUIBMITTALS BY
 REQUEST.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  