2020-03-19 18:52:531ST REVIEW FBC-2017 PLUMBING
 PERMIT #20020362
 3/19/20
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH EDITION
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1.1 & A3.1: THE PLANS SHALL BE DESIGNED IN
 ACCORDANCE WITH THE FBC PLUMBING AND ACCESSIBILITY-
 2017 SIXTH EDITIONS. PLEASE PROVIDE COMPLETE CODE DATA
 ON THE PLANS- SECTION 107.2.1WPB.
  
 2) SHEET A3.1: ENLARGED BATHROOM DETAILS ARE PROVIDED
 FOR WOMEN BUT NOT MEN- SECTION 213.2 FBC ACC.
  
 3) A3.1: PROVIDE THE CLEAR FLOOR SPACE DIMENSIONS AS
 SHOWN ON THE DRAWINGS FOR THE WATER CLOSET- SECTION
 604.3, AND THE SPACE BEYOND THE ARC OF THE DOOR-
 SECTION 603.2.3 (2) FBC ACC.
  
 4) A3.1 DETAIL 02: SHOW THE MINIMUM LENGTH OF THE REAR
 WALL GRAB BAR AND MINIMUM LENGTH EXTENSIONS ON EACH
 SIDE OF THE CENTERLINE- SECTION 604.5.2 FBC ACC.
  
 5) A3.1 DETAIL 03: SHOW THE MINIMUM 42" LENGTH OF THE
 SIDE WALL GRAB BAR, AND THE MINIMUM 54" REQUIRED
 EXTENSION FROM THE REAR WALL- SECTION 604.5.1 FBC ACC.
  
 6) A3.1 DETAIL 03: THE MEASUREMENT FROM THE FRONT OF
 THE WATER CLOSET TO THE CENTERLINE OF THE TOILET PAPER
 DISPENSER SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM- SECTION 604.7 FBC ACC.
  
 7) A3.1 & P401: SHOW THE LOCATIONS OF THE SHOWER
 CONTROLS- SECTION 608.5.3 FBC ACC.
  
 8) A3.1: PLEASE SHOW THE 6' MAXIMUM SPACE FROM ADJACENT
 WALLS OF THE SHOWER TO THE GRAB BARS- SECTION 608.3.3
 FBC ACC.
  
 9) A3.1 & P001: VERIFY THE SHOWER SPRAY UNIT HAS A
 MINIMUM 59" LONG HOSE, CAN BE USED BOTH AS A FIXED
 POSITION SHOWER HEAD AND AS A HAND-HELD SHOWER, AND HAS
 AN ON/OFF CONTROL WITH A NON-POSITIVE SHUT-OFF- SECTION
 608.6 FBC ACC.
  
 10) A3.1: SHOW THE HEIGHT OF THE SHOWER ENTRY
 THRESHOLD- SECTION 608.7 FBC ACC. PLEASE NOTE MAXIMUM
 1/2" ALLOWED.
  
 11) A3.1: PROVIDE ENLARGED DRINKING FOUNTAIN DETAILS
 SHOWING THE REQUIRED CLEAR FLOOR SPACE, SPOUT HEIGHT,
 AND SPOUT LOCATION- SEE SECTIONS 602.2, 602.4, AND
 602.5 FBC ACC.
  
 12) P001: PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 EWH AND SHOW COMPLIANCE WITH THE MINIMUM PERFORMANCE
 CRITERIA LISTED IN TABLE C404.2 FBC EC.
  
 13) P001: VERIFY THE CIRCULATION PUMP HAS CONTROLS THAT
 WILL TURN OFF THE PUMP WHEN THE WATER IN THE
 CIRCULATION LOOP HAS REACHED THE DESIRED TEMPERATURE,
 AND WHEN THERE IS NO DEMAND FOR HOT WATER- SECTION
 C404.6.1 FBC EC.
  
 14) P001: PLEASE INCLUDE THE LAVATORY FAUCETS IN THE
 FIXTURE SCHEDULE- C404.12.2 FBC EC.
  
 15) P402 & P601: SHOW THE REQUIRED TRAP PRIMER FOR THE
 FLOOR DRAIN- SECTION 1002.4 FBC P.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  