| Date |
Text |
| 2020-03-19 18:52:53 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT #20020362 |
| | 3/19/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH EDITION |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A1.1 & A3.1: THE PLANS SHALL BE DESIGNED IN |
| | ACCORDANCE WITH THE FBC PLUMBING AND ACCESSIBILITY- |
| | 2017 SIXTH EDITIONS. PLEASE PROVIDE COMPLETE CODE DATA |
| | ON THE PLANS- SECTION 107.2.1WPB. |
| | |
| | 2) SHEET A3.1: ENLARGED BATHROOM DETAILS ARE PROVIDED |
| | FOR WOMEN BUT NOT MEN- SECTION 213.2 FBC ACC. |
| | |
| | 3) A3.1: PROVIDE THE CLEAR FLOOR SPACE DIMENSIONS AS |
| | SHOWN ON THE DRAWINGS FOR THE WATER CLOSET- SECTION |
| | 604.3, AND THE SPACE BEYOND THE ARC OF THE DOOR- |
| | SECTION 603.2.3 (2) FBC ACC. |
| | |
| | 4) A3.1 DETAIL 02: SHOW THE MINIMUM LENGTH OF THE REAR |
| | WALL GRAB BAR AND MINIMUM LENGTH EXTENSIONS ON EACH |
| | SIDE OF THE CENTERLINE- SECTION 604.5.2 FBC ACC. |
| | |
| | 5) A3.1 DETAIL 03: SHOW THE MINIMUM 42" LENGTH OF THE |
| | SIDE WALL GRAB BAR, AND THE MINIMUM 54" REQUIRED |
| | EXTENSION FROM THE REAR WALL- SECTION 604.5.1 FBC ACC. |
| | |
| | 6) A3.1 DETAIL 03: THE MEASUREMENT FROM THE FRONT OF |
| | THE WATER CLOSET TO THE CENTERLINE OF THE TOILET PAPER |
| | DISPENSER SHALL BE 7 INCHES MINIMUM AND 9 INCHES |
| | MAXIMUM- SECTION 604.7 FBC ACC. |
| | |
| | 7) A3.1 & P401: SHOW THE LOCATIONS OF THE SHOWER |
| | CONTROLS- SECTION 608.5.3 FBC ACC. |
| | |
| | 8) A3.1: PLEASE SHOW THE 6' MAXIMUM SPACE FROM ADJACENT |
| | WALLS OF THE SHOWER TO THE GRAB BARS- SECTION 608.3.3 |
| | FBC ACC. |
| | |
| | 9) A3.1 & P001: VERIFY THE SHOWER SPRAY UNIT HAS A |
| | MINIMUM 59" LONG HOSE, CAN BE USED BOTH AS A FIXED |
| | POSITION SHOWER HEAD AND AS A HAND-HELD SHOWER, AND HAS |
| | AN ON/OFF CONTROL WITH A NON-POSITIVE SHUT-OFF- SECTION |
| | 608.6 FBC ACC. |
| | |
| | 10) A3.1: SHOW THE HEIGHT OF THE SHOWER ENTRY |
| | THRESHOLD- SECTION 608.7 FBC ACC. PLEASE NOTE MAXIMUM |
| | 1/2" ALLOWED. |
| | |
| | 11) A3.1: PROVIDE ENLARGED DRINKING FOUNTAIN DETAILS |
| | SHOWING THE REQUIRED CLEAR FLOOR SPACE, SPOUT HEIGHT, |
| | AND SPOUT LOCATION- SEE SECTIONS 602.2, 602.4, AND |
| | 602.5 FBC ACC. |
| | |
| | 12) P001: PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | EWH AND SHOW COMPLIANCE WITH THE MINIMUM PERFORMANCE |
| | CRITERIA LISTED IN TABLE C404.2 FBC EC. |
| | |
| | 13) P001: VERIFY THE CIRCULATION PUMP HAS CONTROLS THAT |
| | WILL TURN OFF THE PUMP WHEN THE WATER IN THE |
| | CIRCULATION LOOP HAS REACHED THE DESIRED TEMPERATURE, |
| | AND WHEN THERE IS NO DEMAND FOR HOT WATER- SECTION |
| | C404.6.1 FBC EC. |
| | |
| | 14) P001: PLEASE INCLUDE THE LAVATORY FAUCETS IN THE |
| | FIXTURE SCHEDULE- C404.12.2 FBC EC. |
| | |
| | 15) P402 & P601: SHOW THE REQUIRED TRAP PRIMER FOR THE |
| | FLOOR DRAIN- SECTION 1002.4 FBC P. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |