Plan Review Notes
Plan Review Notes For Permit 20020362
Permit Number 20020362
Review Stop M
Sequence Number 1
Notes
Date Text
2020-02-26 08:38:041ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020362
 2/26/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) REFER TO SECTION 809.2 FBC EX AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3.1.1 FBC ML. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 3) SHEET M001: DESIGN CONDITONS LISTED ARE INCORRECT.
 A) WEST PALM BEACH SUMMER OUTDOOR DRY BULB IS 91,
 WINTER DRY BULB IS 45. B) OCCUPIED HEATING- 72. REFER
 TO TABLE D101 FBC- 2017 PLUMBING WHICH IS BASED ON
 ASHRAE 183.
  
 4) M201: SHOW THE REQUIRED CLEARANCES FOR THE O/A
 INTAKE- SECTION 401.4 FBC M.
  
 5) M002: CORRECT NOTE #34 SPECIFYING FLEX DUCT LONG
 LENGTH TO BE 6'. FLEX DUCTS SHALL BE SUPPORTED AT 5'
 INTERVALS PER MANUFACTURER'S RECOMMENDATIONS.
  
 6) M802: PROVIDE ENGINEERED DETAILS FOR ANCHORING THE
 NEW CONDENSERS- SECTION 301.15 FBC M.
  
 7) SUBMITTALS: A) MIAMI-DADE NOA OF FL. PRODUCT
 APPROVAL FOR THE O/A LOUVER. B) DUCT SMOKE DETECTOR. C)
 SPACE SENSORS FOR AC CONTROLS OPERATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  