| Plan Review Notes For Permit 20020362 |
| Permit Number |
20020362 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-20 11:58:58 | BUILD OUT - | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) THE OCCUPANCY CLASSIFICATION SHOULD BE "B" PER FBC | | | 303.1.1 | | | 2) PLEASE PROVIDE COMPLETE COPIES OF THE MIAMI DADE OR | | | FLORIDA STATE PRODUCT APPROVALS FOR THE NEWLY INSTALLED | | | STORE FRONT GLAZING, DOORS AND LOUVERS - (FBC EXISTING | | | BUILDING 702.6) FBC BUILDING 1609.1.2 AND 1609.1.2.1 | | | 3) PLEASE SHOW THE WIND DESIGN CRITERIA AND COMPONENT | | | (WINDOW/DOOR) PRESSURES REQUIRED. FBC 1603.1.4 | | | 4) PLEASE SHOW THE EXISTING EXIT DOOR LOCKS AND LATCHES | | | TO COMPLY WITH FBC 1010.1.9.3 AND ANY REQUIRED DOOR | | | LOCKING SIGNAGE TO COMPLY WITH FBC 1010.1.9.3 (2.2) | | | 5) PLEASE SHOW THE WALL AND CEILING INSULATION R VALUE | | | AND TYPE TO MEET OR EXCEED THE R VALUE SHOWN ON THE | | | ENERGY CALCS. (ENERGY CALCS. NOT YET SUPPLIED). | | | 6) ALL DRAWINGS IN "PROJECT DOX" NEED TO BE | | | ELECTRONICALLY SIGNED AND SEALED. | | | | | | |
|