Plan Review Notes
Plan Review Notes For Permit 20020348
Permit Number 20020348
Review Stop E
Sequence Number 1
Notes
Date Text
2020-02-12 10:49:31FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 THIS UNIT IS BEING FED BY MORE THAN ONE CIRCUIT SO A
 PANEL BOARD AND GROUNDING SYSTEM NEEDS TO BE INSTALLED
 AT THE SEPARATE BUILDING.
  
 225.30 NUMBER OF SUPPLIES
 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE
 SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS
 PERMITTED IN 225.30(A) THROUGH (E).


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved