| 2020-02-12 15:08:11 | 02/12/2020 1ST PLUMBING/GAS REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS OF AN |
| | UPDATED VERSION FOR THE GENERATOR AND THEY SHALL BE |
| | ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR SHALL BE |
| | LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE GENERATOR |
| | SHALL MEET THE REQUIREMENTS OF UL 2200. |
| | 2. THE GENERATOR THAT YOU HAVE STATED ON YOUR PLANS |
| | SAYS 308 BTU'S AND THEY ARE 330 BTU'S ON THE SPEC SO |
| | PLEASE MAKE SURE THAT IS REFLECTED ON YOUR ISOMETRIC |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 3. PLEASE LABEL AND SHOW THE SHUTOFF VALVE AND DRIP LEG |
| | ON GAS ISOMERIC PER THE 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |