| 2020-03-30 09:42:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS |
| | OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. THE RISER |
| | PROVIDED SHOWS TWO METERS FEEDING ONE PANEL, WHICH IS |
| | NOT PERMITTED. ARE THERE SEPARATE PANELS FOR EACH UNIT? |
| | IS THIS SERVICE EXISTING OR PROPOSED? PROVIDE |
| | CLARIFICATIONS AND CORRECTIONS AS NEEDED. NEC 215.5, |
| | 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; WPB FBC 107.2.1 |
| | 2. PLAN IS NOT CLEAR WHAT IS PROPOSED AND WHAT IS |
| | EXISTING. PROVIDE CLEAR INDICATION OF PROPOSED WORK. |
| | WPB FBC 107.2.1 |
| | 3. PROVIDE ACCURATE PANEL SCHEDULE INDICATING ANY NEW |
| | OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. THE CIRCUITS FOR EACH |
| | UNIT MUST BE ACCESSIBLE FOR TO THE OCCUPANT OF THAT |
| | UNIT. THE PANEL SCHEDULE PROVIDED SHOWS CIRCUITS FOR |
| | UNIT A AND B IN THE SAME PANEL. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. NEC 210.8, 210.12, 210.19, 210.20, |
| | 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE |
| | E3602.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |