Plan Review Notes
Plan Review Notes For Permit 20020297
Permit Number 20020297
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-02-12 14:22:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 I HAVE NO OBJECTION TO A FIRE ALARM INSTALL; HOWEVER, I
 WANT TO BE SURE THAT THIS INSTALL IS NOT BE REQUIRED
 THROUGH MY OFFICE WITHOUT SPECIFIC CODE REVIEW
  
  
 1) WHAT IS THE OCCUPANCY PER NFPA 101?
  
  
 2) WHO OR WHAT IS REQUIRING/REQUESTING THIS INSTALL?
  
  
 3) THERE IS AN INDICATION OF A FIRE ALARM SYSTEM BEING
 INSTALLED IN AN EXISTING TRIPLEX OCCUPANCY.
  
 PER NFPA 31 EXISTING APARTMENT OCCUPANCIES A FIRE ALARM
 IS NOT REQUIRED.
  
 31.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 31.3.4.1 GENERAL.
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH
 MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING
 THE REQUIREMENTS
 OF 31.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 31.3.4.2
 THROUGH 31.3.4.5.
 31.3.4.1.2 A FIRE ALARM SYSTEM SHALL NOT BE REQUIRED
 WHERE EACH
 DWELLING UNIT IS SEPARATED FROM OTHER CONTIGUOUS
 DWELLING UNITS BY FIRE
 BARRIERS (SEE SECTION 8.3) HAVING A MINIMUM ?-HOUR FIRE
 RESISTANCE
 RATING, AND WHERE EACH DWELLING UNIT HAS EITHER ITS OWN
 INDEPENDENT EXIT
 OR ITS OWN INDEPENDENT STAIRWAY OR RAMP DISCHARGING AT
 THE FINISHED
 GROUND LEVEL.
  
 PLEASE PROVIDE A BRIEF REVIEW OF WHO IS REQUESTING OR
 REQUIREING THIS INSTALL.
  
 THE ABOVE COMMENT IS STATED DUE TO THE FOLLOWING REVIEW
 OF THE PROPSOED SYSTEM:
  
  
 THE SUBMITTED PLANS APPEARS TO BE OVER DESIGNED WITH
 NUMEROUS POTENIAL EQUIPMENT THAT IS NOT REQUIRED AND
 MAY LEAD TO FALSE ALARMS.
  
  
 4) PLEASE PROVIDE A DETAILED REVIEW OF THE SPECIFIC
 CODE REFERNCES THAT REQUIRE:
  
 A. PULL STATIONS IN RESIDENTIAL UNITS.
 B. THREE HORN STROBES IS SUCH CLOSE PROXIMITY OF EACH
 OTHER IS SUCH SMALL UNITS.
 C. A FACP IN A RESIDENTIAL UNIT.
 D. AN ANNUCIATOR PANEL IS INDICATED SOMEWHERE ON THE
 OUTSIDE; HOWEVER, NO PROTECTION IS INDICATED NOR ITS
 LOCATION, FUNCTIONALITY, SEQUENCE OF OPERATION,
 SECURITY/FD ACCESS ONLY.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved