| 2020-02-19 10:53:13 | 1ST REVIEW: 20020292 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A-4 SHOW CLEAR FLOOR SPACE FOR TOILETS. PER FBC |
| | ACC 604.3.1 |
| | |
| | 2. SHT A-4 SHOW THE DIMENSIONS ON THE CLEAR FLOOR SPACE |
| | ON THE LAVATORY AND TOILET. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 3. SHT. A-4 THE TOP RIM OF THE LAVATORY SHALL BE 34" |
| | MAX PER FBC ACC 606.3 |
| | |
| | 4. SHT. A-4 THE BOTTOM EDGE OF THE REFLECTIVE SURFACE |
| | OF THE MIRROR SHALL BE MAX OF 40". PER FBC ACC 603.3 |
| | |
| | 5. PLEASE PROVIDE A SANITARY AND WATER ISOMETRIC |
| | DRAWING. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. TEMPERED WATER REQUIRED AT THE LAVATORY'S DELIVERED |
| | THROUGH A TEMPERATURE LIMITING DEVICE COMPLYING WITH |
| | ASSE 1070 OR CSA B125.3 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |