| 2020-02-25 13:23:00 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHEET E-1 DOES NOT HAVE THE ARCHITECTS SEAL AND |
| | SIGNATURE. PER THE WPB AMENDMENTS TO THE FBC, PLAN |
| | (EACH SHEET OF BOTH COPIES) IS REQUIRED TO BEAR THE |
| | NAME AND BE SIGNED AND SEALED BY THE PERSON RESPONSIBLE |
| | FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, |
| | 107.2; FS 471, 481 |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH |
| | CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, 408.4; |
| | WPB FBC 107.3.5 |
| | 3. RECEPTACLE OUTLETS IN BATHROOMS REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | 4. PROVIDE SCOPE OF WORK DETAIL. WPB FBC 107.2.1 |
| | 5. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |