| Plan Review Notes For Permit 20020286 |
| Permit Number |
20020286 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-07 19:02:32 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1-FLAT ROOF NOA 18-0919.12 SUBMITTED: SELECTED ASSEMBLY | | | ON PAGE 53 OF 67 DOESN'T MEET THE DESIGN PRESSURES FOR | | | ALL ROOF ZONES. PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER | | | AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE | | | OF NOA. NEED THE CALCULATIONS TO MEET THE DESIGN | | | PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|