| 2020-02-18 13:34:56 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20020258 |
| | ADD: 5600 N. FLAGLER DR. SUITE: PH206 |
| | CONT: WALL TO WALL WE DO IT ALL |
| | TEL: 561-463-9708 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. FEB. 18TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 1 PALM BEACH HOUSE FLOOR PLAN OF UNIT NOT TO |
| | SCALE, SMALLER THAN 1/8 INCH SCALE. 2017 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1 ADMINISTRATIVE CODE 107.2.1.3 QUALITY OF BUILDING |
| | PLANS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 |
| | INCH SCALE UPON SUBSTANTIAL PAPER. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | |
| | 2) 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE |
| | THE EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |
| | 3) 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. THE |
| | PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK |
| | INDICATES INSTALL TILE, DRYWALL, PART. PLEASE PROVIDE A |
| | BETTER DESCRIPTION OF WORK. SHEET 2 OF 3 IT WOULD |
| | APPEAR THERE IS STILL A TUB IN THE BATHROOM BUT SHEET 3 |
| | OF 3 IT WOULD APPEAR THE TUB HAS BEEN REMOVED AND A NEW |
| | SHOWER, (5 INCH CURB) IS BEING PROPOSED. |
| | |
| | 4) FOR NEW SUB-SURFACES/ BASE FOR TILE MUST SHOW |
| | COMPLIANCE WITH 2509.2 OF THE 2017 FBC-B: |
| | GLASS MAT GYPSUM BACKING PANEL ASTM C1178 |
| | NONASBESTOS FIBER-CEMENT BACKER BOARD ASTM C1288 OR ISO |
| | 8336 CATEGORY C |
| | NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER |
| | UNIT ASTM C1325 |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |