| Plan Review Notes For Permit 20020236 |
| Permit Number |
20020236 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-03-23 16:13:00 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE L-401 THIS PAGE SHOWS A FEW PLANTERS WITH 120 VOLT | | | LIGHTS IN THE PLANTERS, THESE WILL NEED TO BE GFCI | | | PROTECTED BECAUSE OF THE LOCATION 680.22(B)(4) | | | | | | PAGE E3.0 SEEMS TO BE A DUPLICATE OF E1.0 AND BY A | | | DIFFERENT ENGINEER. PLEASE CLARIFY | | | | | | GFCI PROTECTION FOR PUMPS WHERE IS IT LOCATED HOW MANY | | | PUMPS? IF IN THE SET WHICH PAGE? |
|