| 2020-07-08 11:42:19 | 1ST REVIEW FBC-2017 RES. PLUMBING |
| | PERMIT- 20020232 |
| | 7/8/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: THE GAS WATER HEATER HAS BEEN REMOVED FROM |
| | THE ACCESSORY BUILDING. INDICATE HOW HOT WATER IS TO BE |
| | PROVIDED FOR BATHING, WASHING, AND CULINARY PURPOSES- |
| | SECTION P2801.1 FBC RES. |
| | |
| | 2) P1 & P2- HOUSE BATH: CLARIFY THE LOCATION OF THE DRY |
| | VENT CONNECTION FOR THE WET VENTED BATH FIXTURES- REFER |
| | TO SECTION P3108.2.1 FBC RES- WHERE THE DRY VENT |
| | CONNECTS TO A WATER CLOSET FIXTURE DRAIN, THE DRAIN |
| | SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL WET VENT |
| | SYSTEM. NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN |
| | SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE |
| | DRAIN CONNECTION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |