Plan Review Notes
Plan Review Notes For Permit 20020232
Permit Number 20020232
Review Stop G
Sequence Number 5
Notes
Date Text
2020-07-24 14:22:16PLAN REVIEW - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 5TH REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 4TH REVIEW HAVE NOT BEEN ADDRESSED. SEE
 BELOW.
  
 7/8/2020
  
 4TH FUEL GAS REVIEW - CC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G.1 CORRECTIONS REQUIRED:
 A) KEYNOTE #8 LOW PRESSURE REGULATOR: RELOCATE THE
 LOW-PRESSURE REGULATOR ON THE ISO AND FLAT LINE DRAWING
 TO A LOCATION UPSTREAM OF THE TEE SEPARATING THE BRANCH
 LINES TO THE WATER HEATER AND THE RANGE AND DRYER.
 OTHERWISE IT APPEARS THAT 2 PSI GAS PRESSURE IS BEING
 DELIVERED TO THE RANGE AND DRYER- SECTION G2421.1 FBC
 RES.
 B) CORRECT THE PIPE SIZING TABLES LISTED BELOW THE ISO
 TO MATCH THE CORRECT TABLES SHOWN IN THE GAS SIZING
 SCHEDULE- G2413.4 FBC RES.
 C) ADD THE PE TABLE AND THE TDL UNDER THE ISO- G2413.4.
  
 2) G.1: INDICATE HOW MAKEUP AIR WILL BE PROVIDED FOR
 THE DRYER- SECTIONS G2407.1 & G2439.5 FBC RES.
  
 3) G.1: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE BBQ GRILL AND PROVIDE AN
 EQUIPMENT SCHEDULE ON THE PLAN- SECTION G2447.1. PLEASE
 NOTE THAT THE APPLIANCE SHALL BE TESTED IN ACCORDANCE
 WITH ANSI Z21.1 OR ANSI Z21.58 AND SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE
 PLAN SHOWS THE APPLIANCE TO BE INSTALLED UNDER A
 COVERED PATIO WHICH MAY REQUIRE A HOOD AND DUCTED VENT
 SYSTEM. ADDITIONAL INFORMATION IS REQUIRED PER
 MANUFACTURER'S SPECIFICATIONS. PLEASE NOTE COMPLETE
 EXHAUST VENTILATION SYSTEM PLANS AND PRODUCT SUBMITTALS
 MAY BE REQUIRED, INCLUDING DIMENSIONED TOP AND FRONT
 VIEW DRAWINGS OF THE BBQ AND VENT SYSTEM SHOWING THE
 HOOD AND VENT SIZES, LENGTH OF VENT RUN AND TERMINATION
 LOCATION, AND CLEARANCES TO COMBUSTIBLES- SECTION
 107.2.1 WPB.
  
  
  