| 2020-05-12 08:21:07 | 3RD REVIEW FBC-2017 RESIDENTIAL GAS |
| | PERMIT #20020232 |
| | 5/12/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 201 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P1. 2ND REQUEST FOR A COMPLETE GAS ISOMETRIC. |
| | |
| | A) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE GAS PIPING |
| | RUN FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET- SECTIONS G2413.4.1 AND G2513.4.2 FBC RES. THIS |
| | INCLUDES THE NEW RUN TO THE WATER HEATER AT THE |
| | ACCESSORY STRUCTURE WHICH IS SHOWN IN A SEPARATE |
| | ISOMETRIC DRAWING. PROVIDE ONE ISOMETRIC THAT CONTAINS |
| | MAIN HOUSE AND ACCESSORY STRUCTURE PIPING UNLESS THE |
| | INTENSION IS TO PROVIDE A SEPARATE METER AT THE |
| | ACCESSORY STRUCTURE. |
| | B) PROVIDE THE TOTAL GAS LOAD WHICH INCLUDES THE TWO |
| | WATER HEATERS AND THE RANGE IN THE MAIN HOUSE- SECTION |
| | G2413.3 & G2413.4 FBC RES. THE CURRENT ISOMETRIC |
| | INDICATES A TOTAL LOAD OF 470 MBH, HOWEVER THE TOTALS |
| | INDICATED IN THE KEYNOTES AND COMBUSTION AIR CALC IS |
| | 404.2 MBH. |
| | C) PROVIDE THE TYPES AND SIZES OF GAS PIPING, AND LIST |
| | THE PIPE SIZING TABLES USED FROM THE FBC RES. IT WOULD |
| | APPEAR THAT UNDERGROUND PIPING WILL BE REQUIRED TO |
| | SUPPLY THE WATER HEATER AT THE ACCESSORY STRUCTURE- SEE |
| | TABLES G2413.4(1) ? G2413.4(21) FBC RES. |
| | D) SHOW THE LOCATIONS OF REGULATORS AT THE APPLIANCES |
| | WHERE REQUIRED TO REDUCE PRESSURE. PLEASE NOTE WHERE MP |
| | REGULATORS ARE INSTALLED, INDICATE A UNION WITHIN 1 FT. |
| | OF EITHER SIDE OF THE REGULATOR- SECTIONS G2420.4 AND |
| | 2421.2(7) FBC RES. |
| | |
| | 2) P1: SHOW THE UNDERGROUND GAS PIPING RUN BETWEEN THE |
| | MAIN HOUSE AND ACCESSORY STRUCTURE- SECTION 107.2.1 |
| | WPB. |
| | |
| | 3) P1: 2ND REQUEST FOR SUBMITTAL OF MANUFACTURER?S |
| | SPECIFICATIONS AND INSTALLATION GUIDELINES FOR THE |
| | WATER HEATERS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |