| 2020-02-10 16:12:41 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- ROOF TILE FLORIDA PRODUCT APPROVAL FL17152-R3 AND |
| | ROOF TILE ADHESIVE FLORIDA PRODUCT APPROVAL FL6332-R8 |
| | SUBMITTED: CLEARLY MARK ADHESIVE PADDY SIZE AS REQUIRED |
| | BY CITY POLICY FOR ALL ROOFING PERMITS TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 2- ROOFING UNDERLAYMENT TU PLUS-MAX FLORIDA PRODUCT |
| | APPROVALS FL5259-R29 SUBMITTED: |
| | CLEARLY MARK WHICH MAXIMUM DESIGN PRESSURES ASSEMBLY |
| | FROM SEC. 5.6.1 OF PRODUCT APPROVAL IS GOING TO BE |
| | USED. OR IF USING THE FRSA/TRI APRIL 2012 (04-12) |
| | REVISED EDITION, THEN PROVIDE COMPLETE INFORMATION |
| | SHOWING THE DETERMINATION OF DESIGN WIND LOADS AND |
| | UNDERLAYMENT FASTENING AS REQUIRED BY SEC. 5.6.1 OF |
| | PRODUCT APPROVAL SUBMITTED. |
| | |
| | 3- IT IS NOT CLEAR WHY SUBMITTING FLAT ROOF FLORIDA |
| | PRODUCT APPROVAL FL16709-R6. COVER PAGE STATES "PG 3 OF |
| | 4 MODIFIED FOR THE UNDERLAYMENT ONLY". IS THIS THE |
| | UNDERLAYMENT FOR THE TILE ROOF?. IF SO, THIS IS A FLAT |
| | ROOF ASSEMBLY NOT AN UNDERLAYMENT FOR ROOF TILE. THE |
| | UNDERLAYMENT FOR THE ROOF TILE IS THE TU PLUS PRODUCT |
| | APPROVAL SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS. |
| | ***NOTE: |
| | 02/10/2020 TALKED TO BRITNI FROM STORM ROOFING. SHE |
| | SAID THEY ARE INSTALLING THE MODIFIED MEMBRANE |
| | (FLINTLASTIC GMS) ON TOP OF THE TU PLUS. THIS WILL BE |
| | THE UNDERLAYMENT FOR THE ROOF TILE. I TOLD BRITNI THE |
| | PROPOSED INSTALLATION IS NOT AN APPROVED SYSTEM. TOLD |
| | HER THE PROPOSED INSTALLATION COULD BE SUBMITTED AS AN |
| | ALTERNATIVE MATERIALS AND METHODS SEC. 104.11 CITY |
| | AMENDMENTS. DISCUSSED THIS ISSUE WITH ROBERT BROWN |
| | (BUILDING OFFICIAL). HE AGREED, PROPOSED INSTALLATION |
| | NEEDS TO BE SUBMITTED AS ALTERNATIVE MATERIALS AND |
| | METHODS. THEREFORE, NEED TO PROVIDE COMPLETE DATA |
| | SHOWING THAT THE PROPOSED INSTALLATION WILL WORK. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |