Plan Review Notes
Plan Review Notes For Permit 20020213
Permit Number 20020213
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-02-10 11:23:32THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATION OF A FLOOR/SEATING PLAN.
  
 WHAT WILL THIS TENT BE USED FOR?
  
 WAHT IS THE NUMBER OF PROPOSED OCCUPANTS?
  
 A FLOOR/SEATING PLAN IS REQUIRED.
  
  
  
 2) THERE ARE NO INDICATIONS IF THE TENT WILL HAVE SIDES
 OR EXIT DOORS.
  
 PLEASE PROVIDE FOR EXITING PER THE NUMBER OF OCCUPANTS.
  
  
  
 3) WILL THIS TENT BE USED AT NIGHT?
  
 HOW WILL THE ELECTFICITY/LIGHTING BE PROVIDED?
  
  
  
 4) WHERE WILL THE TENT BE LOCATED?
  
 PER NFPA 1 CH 25
  
 25.2.1.2 TENTS SHALL BE ERECTED TO COVER NOT MORE THAN
 75 PERCENT
 OF THE PREMISES, UNLESS OTHERWISE APPROVED BY THE AHJ.
  
 25.2.3.3 TENTS NOT OCCUPIED BY THE PUBLIC AND NOT USED
 FOR THE
 STORAGE OF COMBUSTIBLE MATERIAL SHALL BE PERMITTED TO
 BE ERECTED
 LESS THAN 10 FT (3050 MM) FROM OTHER STRUCTURES WHERE
 THE AHJ
 DEEMS SUCH CLOSE SPACING TO BE SAFE FROM HAZARD TO THE
 PUBLIC.
  
 25.2.3.5 THE PLACEMENT OF TENTS RELATIVE TO OTHER
 STRUCTURES SHALL
 BE AT THE DISCRETION OF THE AHJ, WITH CONSIDERATION
 GIVEN TO
 OCCUPANCY, USE, OPENING, EXPOSURE, AND OTHER SIMILAR
 FACTORS.
  
 25.2.4 FIRE HAZARDS.
 25.2.4.1 THE FINISHED GROUND LEVEL ENCLOSED BY ANY
 TENT, AND THE
 FINISHED GROUND LEVEL FOR A REASONABLE DISTANCE, BUT
 FOR NOT LESS
 THAN 10 FT (3050 MM) OUTSIDE OF SUCH A TENT, SHALL BE
 CLEARED OF ALL
 FLAMMABLE OR COMBUSTIBLE MATERIAL OR VEGETATION THAT IS
 NOT USED
 FOR NECESSARY SUPPORT EQUIPMENT. THE CLEARING WORK
 SHALL BE
 ACCOMPLISHED TO THE SATISFACTION OF THE AHJ PRIOR TO
 THE ERECTION
 OF SUCH A TENT. THE PREMISES SHALL BE KEPT FREE FROM
 SUCH
 FLAMMABLE OR COMBUSTIBLE MATERIALS DURING THE PERIOD
 FOR WHICH
 THE PREMISES ARE USED BY THE PUBLIC. [101: 11.11.4.1]
  
  
 PLEASE PROVIDE A SITE PLAN INCLUDING PROPOSED
 DIMESNIONS FOR PROPERTY LINES AND OTHER STRUCTURES.
  
  
  
 5) THERE ARE NO INDICATIONS OF NO SMOKING SIGNS
  
 25.2.4.2 SMOKING.
 25.2.4.2.1 SMOKING SHALL NOT BE PERMITTED IN ANY TENT,
 UNLESS
 APPROVED BY THE AHJ. [101: 11.11.4.2.1]
 25.2.4.2.2 IN ROOMS OR AREAS WHERE SMOKING IS
 PROHIBITED, PLAINLY
 VISIBLE SIGNS SHALL BE POSTED THAT READ AS FOLLOWS:
 NO SMOKING
  
 PLEASE PROVIDE
  
  
  
 6) THERE ARE NO INDICATIONS OF FIRE EXTINGUISHERS
  
 25.2.5 FIRE-EXTINGUISHING EQUIPMENT. PORTABLE
 FIREEXTINGUISHING
 EQUIPMENT OF APPROVED TYPES SHALL BE FURNISHED AND
 MAINTAINED IN TENTS IN SUCH QUANTITY AND IN SUCH
 LOCATIONS AS
 DIRECTED BY THE AHJ.
  
 PLEASE PROVIDE CERTIFIED 5LB ABC EXTINGUISHERS WITHIN
 75FT TRAVLE DISTANCE.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  