| Notes |
| Date |
Text |
| 2020-02-08 11:55:14 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A | | | SPAN OF 40' OR GREATER IN ANY DIRECTION: | | | A. PROVIDE DETAILS FOR STRUCTURAL CONNECTIONS. | | | B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. | | | THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY | | | A DESIGN PROFESSIONAL. | | | | | | 2) FBC B TABLE 2902.1, ON SITE PLAN SHOW THE LOCATION | | | OF SANITARY FACILITIES/RESTROOMS (PERMANENT AND/OR | | | PORTABLE) AS PER THE REQUIREMENTS OF TABLE 2902.1 OF | | | THE FLORIDA BUILDING CODE. | | | NOTE: PROVIDE LOCATION OF ACCESSIBLE ROUTE FROM TENT TO | | | ACCESSIBLE RESTROOMS ON SITE PLAN. THE ACCESSIBLE | | | RESTROOMS SHALL BE LOCATED WITHIN 500' OF TENT. | | | | | | 3) FBC A 402 PROVIDE LOCATION OF ACCESSIBLE ROUTE FROM | | | PARKING TO TENT ENTRANCE. | | | | | | 4) FBC B 602, ON SITE PLAN SHOW THE DISTANCE TO LOT | | | LINES AND OTHER STRUCTURES. |
|