Plan Review Notes
Plan Review Notes For Permit 20020211
Permit Number 20020211
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-02-12 11:33:24THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THERE ARE GLASS SLIDING DOORS INDICATED' THEY SHALL
 COMPLY WITH NFPA101, CH 7 MEANS OF EGRESS:
  
 7.2.1.4 SWING AND FORCE TO OPEN.
  
 (4) HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE
 PERMITTED UNDER
 ANY OF THE FOLLOWING CONDITIONS:
 (A) HORIZONTAL-SLIDING DOOR ASSEMBLIES IN DETENTION AND
 CORRECTIONAL OCCUPANCIES, AS PROVIDED IN CHAPTERS 22
 AND 23, SHALL BE PERMITTED.
 (B) SPECIAL-PURPOSE HORIZONTALLY SLIDING ACCORDION OR
 FOLDING DOOR ASSEMBLIES COMPLYING WITH 7.2.1.14 SHALL
 BE PERMITTED.
 (C) UNLESS PROHIBITED BY CHAPTERS 11 THROUGH 43,
 HORIZONTAL-SLIDING DOOR ASSEMBLIES SERVING A ROOM OR
 AREA WITH AN OCCUPANT LOAD OF FEWER THAN 10 SHALL BE
 PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE
 MET:
 I. THE AREA SERVED BY THE DOOR ASSEMBLY HAS NO HIGH
 HAZARD CONTENTS.
 II. THE DOOR ASSEMBLY IS READILY OPERABLE FROM EITHER
 SIDE WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
 III. THE FORCE REQUIRED TO OPERATE THE DOOR ASSEMBLY IN
 THE DIRECTION OF DOOR LEAF TRAVEL IS NOT MORE THAN 30
 LBF (133 N) TO SET THE DOOR LEAF IN MOTION AND IS NOT
 MORE THAN 15 LBF (67 N) TO CLOSE THE DOOR ASSEMBLY
 OR OPEN IT TO THE MINIMUM REQUIRED WIDTH.
 IV. THE DOOR ASSEMBLY COMPLIES WITH ANY REQUIRED FIRE
 PROTECTION RATING, AND, WHERE RATED, IS SELF-CLOSING
 OR AUTOMATIC-CLOSING BY MEANS OF SMOKE DETECTION
 IN ACCORDANCE WITH 7.2.1.8 AND IS INSTALLED IN
 ACCORDANCE WITH NFPA 80, STANDARD FOR FIRE
 DOORS AND OTHER OPENING PROTECTIVES.
 V. CORRIDOR DOOR ASSEMBLIES REQUIRED TO BE SELFLATCHING
 HAVE A LATCH OR OTHER MECHANISM THAT
 ENSURES THAT THE DOOR LEAF WILL NOT REBOUND INTO A
 PARTIALLY OPEN POSITION IF FORCEFULLY CLOSED.
  
  
 2) THERE ARE NEW WALLS INDICATED. AN EVALUATION OF THE
 FIRE SPRINKLER PROTECTION IS REQUIRED.
  
 THOUGH SPRINKLERS MAY BE EXISTING THE NEW WALLS MAY
 REQUIRE SPRINKLER HEAD COVERAGE MODIFICATIONS.
  
 ANY SPRINKLER WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL