| 2020-02-27 14:14:07 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16730-R24 |
| | SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS |
| | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: |
| | IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | RESPONSE: |
| | IT IS NOT CLEAR WHICH APPROVED ASSEMBLY IS GOING TO BE |
| | INSTALLED. ENGINEER IS REFERENCING AND OLD FLORIDA |
| | PRODUCT APPROVAL FL16730-R22. ENGINEER IS SPECIFYING |
| | SYSTEM W-56 ON PAGE 14 OF 100. ACCORDING TO THE OLD |
| | FLORIDA PRODUCT APPROVAL, THIS IS A NON-INSULATED |
| | SYSTEM. FLORIDA PRODUCT APPROVAL THAT WAS SUBMITTED IS |
| | FL16730-R24 AND IS MARKED WITH ASSEMBLY W-54 WHICH IS |
| | AN INSULATED ASSEMBLY. REVISE AS REQUIRED TO MATCH. |
| | NOTE: ENGINEER NEEDS TO REFERENCE THE CURRENT FLORIDA |
| | PRODUCT APPROVAL FL 16730-R24 TO AVOID CONFLICTS |
| | DELAYS. RE-SUBMIT REVISED RAS 117 CALCULATIONS SHOWING |
| | THE CORRECT ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS. |
| | (PROVIDE 2 COPIES. ONLY ONE WAS SUBMITTED). |
| | |
| | 2- OK. |
| | |
| | 3- OK. |
| | |
| | 4- OK |
| | |
| | 5- OK. |
| | |
| | |
| | PROVISO: |
| | 8/12 ROOF TILE SLOPE REQUIRES EVERY TILE TO BE FASTENED |
| | IN ADDITION TO THE ADHESIVE. SEE PAGE 9 OF FRSA/TRI 5TH |
| | EDITION REVISED AND SEC. R905.3.2 FBC-RESIDENTIAL. |
| | |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |