| 2021-04-23 14:36:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE NEW SITE SHEET SUBMITTED IS NO BETTER THAN THE |
| | OLD ONE AND NO MANUFACTURERS SPECIFICATION SHEETS WERE |
| | SUBMITTED. |
| | |
| | THE UNDERGROUND FIRE LINE IS REQUIRED TO BE INSTALLED, |
| | TESTED AND INSTALLED PER NFPA 24. |
| | |
| | FOR DISCUSSION AND REQUIREMENT PURPOSES, THIS WORK HAS |
| | ALREADY BEEN COMPLETED. |
| | |
| | IT HAS ALSO NOT BEEN INSPECTED. |
| | |
| | THE FIRE DEPARTMENT HAS NOT SEEN NOR WITNESSED NOR |
| | TESTED NOR INSPECTED THIS WORK. |
| | |
| | PLEASE HIGHLIGHT ON THE NEW SITE SHEET WHERE ALL THE |
| | FIRE LINE PIPE IS EXACTLY AND PROVIDE THE EQUIPMENT |
| | SPEC SHEETS FOR THE INSTALLED EQUIPMENT. |
| | |
| | ON APPROVAL OF THIS PERMIT AFTER THE ABOVE INFORMATION |
| | IS RECEIVED, AN INSPECTION SHOULD BE CALLED IN. A (1) |
| | UNDERGROUND JOINT SHALL BE DUG OUT, AT THE CONTRACTOR |
| | AND INSPECTOR AGREED CHOICE, AND THE BOLTS ON THAT |
| | JOINT WILL BE VERIFIED PER THE SUBMITTED SPEC SHEETS. |
| | |
| | IF THE COLLAR/ BOLTS ARE NOT INSTALLED PER THE |
| | MANUFACTURE, THE INSPECTION WILL FAIL AND ALL THE |
| | JOINTS WILL BE EXPOSED AND CORRECTED. |
| | |
| | IF THE INSPECTION PASSES ON THIS 1 JOINT, I WILL |
| | REQUEST THAT AN EOR SUPPLY A FORMAL SIGNED AND SEALED |
| | LETTER STATING THAT THE REMAINING JOINTS HAVE BEEN |
| | INSTALLED PER THE MANUFACTURE. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND AGREEMENT. |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |