| Plan Review Notes For Permit 20020124 |
| Permit Number |
20020124 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2020-03-28 10:07:08 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E.0 | | | | | | 1) A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A | | | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE | | | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE | | | FEEDER OR BRANCH CIRCUIT. NEC 225.30 | | | | | | 2) PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | | CIRCUIT. NEC 250.32; FBC RE3607.3 | | | | | | 3) PLANS ARE NOT SIGNED. PLAN IS REQUIRED TO BE SIGNED | | | AND SEALED BY THE DESIGN PROFESSIONAL RESPONSIBLE FOR | | | THE DESIGN. FBC 107.2.1, FS 471, 481 | | | | | | | | | |
|