| Date |
Text |
| 2020-03-10 08:45:27 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | 1) ONLY ONE FEEDER AND/OR BRANCH CIRCUIT TO A |
| | STRUCTURE, PLEASE SHOW HOW THIS PLAN MEETS THE |
| | REQUIREMENTS FOR 225.30 (A) THRU (E). |
| | YOU HAVE TWO FEEDERS GOING TO THE MAIN HOUSE FROM THE |
| | GUEST QUARTERS. |
| | |
| | 225.30 NUMBER OF SUPPLIES |
| | A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| | DISCONNECTING MEANS SHALL BE |
| | SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS |
| | PERMITTED IN 225.30(A) THROUGH (E). FOR THE PURPOSE OF |
| | THIS SECTION, A MULTIWIRE |
| | BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE CIRCUIT. |
| | WHERE A BRANCH CIRCUIT OR FEEDER ORIGINATES IN THESE |
| | ADDITIONAL BUILDINGS OR OTHER |
| | STRUCTURES, ONLY ONE FEEDER OR BRANCH CIRCUIT SHALL BE |
| | PERMITTED TO SUPPLY POWER BACK TO THE ORIGINAL BUILDING |
| | OR STRUCTURE, UNLESS |
| | PERMITTED IN 225.30(A) THROUGH (E). |
| | |
| | (A) SPECIAL CONDITIONS. ADDITIONAL FEEDER S OR BRANCH |
| | CIRCUITS |
| | SHALL BE PERMITTED TO SUPPLY THE FOLLOWING: |
| | (1) FIRE PUMPS |
| | (2) EMERGENCY SYSTEMS |
| | (3) LEGALLY REQUIRED STANDBY SYSTEMS |
| | (4) OPTIONAL STANDBY SYSTEMS |
| | (5) PARALLEL POWER PRODUCTION SYSTEMS |
| | (6) SYSTEMS DESIGNED FOR CONNECTION TO MULTIPLE SOURCES |
| | OF |
| | SUPPLY FOR THE PURPOSE OF ENHANCED RELIABILITY |
| | (B) SPECIAL OCCUPANCIES. BY SPECIAL PERMISSION, |
| | ADDITIONAL |
| | FEEDERS OR BRANCH CIRCUITS SHALL BE PERMITTED FOR |
| | EITHER OF THE |
| | FOLLOWING: |
| | (1) MULTIPLE-OCCUPANCY BUILDINGS WHERE THERE IS NO |
| | SPACE |
| | AVAILABLE FOR SUPPLY EQUIPMENT ACCESSIBLE TO ALL |
| | OCCUPANTS |
| | (2) A SINGLE BUILDING OR OTHER STRUCTURE SUFFICIENTLY |
| | LARGE TO |
| | MAKE TWO OR MORE SUPPLIES NECESSARY |
| | (C) CAPACITY REQUIREMENTS. ADDITIONAL FEEDERS OR BRANCH |
| | CIRCUITS SHALL BE PERMITTED WHERE THE CAPACITY |
| | REQUIREMENTS ARE |
| | IN EXCESS OF 2000 AMPERES AT A SUPPLY VOLTAGE OF 1000 |
| | VOLTS |
| | OR LESS. |
| | (D) DIFFERENT CHARACTERISTICS. ADDITIONAL FEEDERS OR |
| | BRANCH |
| | CIRCUITS SHALL BE PERMITTED FOR DIFFERENT VOLTAGES, |
| | FREQUENCIES, OR |
| | PHASES OR FOR DIFFERENT USES, SUCH AS CONTROL OF |
| | OUTSIDE LIGHTING |
| | FROM MULTIPLE LOCATIONS. |
| | (E) DOCUMENTED SWITCHING PROCEDURES. ADDITIONAL FEEDERS |
| | OR |
| | BRANCH CIRCUITS SHALL BE PERMITTED TO SUPPLY |
| | INSTALLATIONS UNDER |
| | SINGLE MANAGEMENT WHERE DOCUMENTED SAFE SWITCHING |
| | PROCEDURES |
| | ARE ESTABLISHED AND MAINTAINED FOR DISCONNECTION. |
| | |
| | 2) SMOKE ALARM/CO COMBONATION IN THE GARAGE PLEASE SHOW |
| | LISTING FOR THIS LOCATION 110.3 |
| | R314.1.1 LISTINGS. |
| | SMOKE ALARMS SHALL BE LISTED IN ACCORDANCE WITH UL 217. |
| | COMBINATION SMOKE AND CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED IN ACCORDANCE WITH UL 217 AND UL 2034 |
| | |
| | 3) GARAGE DOOR OPENERS NOT SHOWN ON GFCI |
| | E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES. |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE RECEPTACLES |
| | INSTALLED IN GARAGES AND GRADE-LEVEL PORTIONS OF |
| | UNFINISHED ACCESSORY BUILDINGS |
| | USED FOR STORAGE OR WORK AREAS SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| | [210.8(A)(2)] |
| | |
| | |