| 2020-02-20 12:02:30 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) SERVICE SEEMS TO BE LOCATED IN THE BUILDING IN THE |
| | BACK OF THE LOT, IF SO ONLY ONE FEEDER CAN BE USED TO |
| | FEED THE HOUSE.PLEASE VERIFY THE LOCATION OF THE |
| | SERVICE!!! |
| | |
| | 225.30 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY |
| | A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A |
| | SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY |
| | ONE FEEDER OR BRANCH CIRCUIT |
| | |
| | E3607.3BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR |
| | BRANCH CIRCUIT(S). |
| | BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH |
| | CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR |
| | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH |
| | SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S) |
| | SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION |
| | E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS |
| | ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING |
| | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) |
| | REQUIRED IN SECTION E3608 SHALL BE INSTALLED. |
| | [250.32(A)] |
| | |
| | EXCEPTION: A GROUNDING ELECTRODE SHALL NOT BE REQUIRED |
| | WHERE ONLY ONE BRANCH CIRCUIT, INCLUDING A MULTIWIRE |
| | BRANCH CIRCUIT, SUPPLIES THE BUILDING OR STRUCTURE AND |
| | THE BRANCH CIRCUIT INCLUDES AN EQUIPMENT GROUNDING |
| | CONDUCTOR FOR GROUNDING THE NONCURRENT-CARRYING PARTS |
| | OF ALL EQUIPMENT. FOR THE PURPOSES OF THIS SECTION, A |
| | MULTIWIRE BRANCH CIRCUIT SHALL BE CONSIDERED AS A |
| | SINGLE BRANCH CIRCUIT. |
| | |
| | 2) SHOW LOCATION OF SERVICE IF SEPARATE FROM THE HOUSE |
| | YOU WILL NEED TO SEE THE ABOVE COMMENT FOR THE FEEDER. |
| | |
| | |