| 2020-02-21 08:52:22 | 2ND REVIEW: 20020124 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: YOU MAY REMOVE GAS FROM MASTER AND SUBMIT |
| | SEPARATELY IN ORDER TO EXPEDITE MASTER PERMIT ISSUANCE. |
| | CONTACT STEVE KENNEDY |
| | |
| | 1. SHT. P1 AND P4 SHOWS STEEL GAS PIPING UNDERGROUND |
| | GALVANIZED STEEL PIPING IS NOT APPROVED FOR UNDERGROUND |
| | INSTILLATION'S THE MOST COMMON PIPING USED FOR THIS IS |
| | A POLYETHYLENE PLASTIC PIPE CONFORMING TO ASTM D2513 . |
| | PER FBC FG 404.11, 403.6 |
| | |
| | 2. SHT. P3 FUEL GAS NOTES #3 GALVANIZED STEEL PIPING IS |
| | NOT APPROVED FOR UNDERGROUND INSTILLATION'S THE MOST |
| | COMMON PIPING USED FOR THIS IS A POLYETHYLENE PLASTIC |
| | PIPE CONFORMING TO ASTM D2513 . PER FBC FG 404.11, |
| | 403.6 |
| | |
| | 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2017 FUEL GAS CODE SEC. 304. |
| | |
| | 4. DRIP LEGS OR DIRT LEGS ARE REQUIRED AT THE GAS |
| | APPLIANCES PLEASE PROVIDE DETAIL OR SHOW ON THE GAS |
| | ISOMETRIC. PER FBC FG 408.2, 408.4 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |