2020-02-21 08:52:222ND REVIEW: 20020124
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS: YOU MAY REMOVE GAS FROM MASTER AND SUBMIT
 SEPARATELY IN ORDER TO EXPEDITE MASTER PERMIT ISSUANCE.
 CONTACT STEVE KENNEDY
  
 1. SHT. P1 AND P4 SHOWS STEEL GAS PIPING UNDERGROUND
 GALVANIZED STEEL PIPING IS NOT APPROVED FOR UNDERGROUND
 INSTILLATION'S THE MOST COMMON PIPING USED FOR THIS IS
 A POLYETHYLENE PLASTIC PIPE CONFORMING TO ASTM D2513 .
 PER FBC FG 404.11, 403.6
  
 2. SHT. P3 FUEL GAS NOTES #3 GALVANIZED STEEL PIPING IS
 NOT APPROVED FOR UNDERGROUND INSTILLATION'S THE MOST
 COMMON PIPING USED FOR THIS IS A POLYETHYLENE PLASTIC
 PIPE CONFORMING TO ASTM D2513 . PER FBC FG 404.11,
 403.6
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2017 FUEL GAS CODE SEC. 304.
  
 4. DRIP LEGS OR DIRT LEGS ARE REQUIRED AT THE GAS
 APPLIANCES PLEASE PROVIDE DETAIL OR SHOW ON THE GAS
 ISOMETRIC. PER FBC FG 408.2, 408.4
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  