Plan Review Notes
Plan Review Notes For Permit 20020124
Permit Number 20020124
Review Stop E
Sequence Number 1
Notes
Date Text
2020-02-19 13:37:01FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) GARAGE AND STORAGE BUILDING APPEARS TO BE A SEPARATE
 STRUCTURE AND SHALL BE WIRED AS SUCH,
  
 E3607.3BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S).
 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH
 CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH
 SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S)
 SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION
 E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS
 ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S)
 REQUIRED IN SECTION E3608 SHALL BE INSTALLED.
 [250.32(A)]
  
 EXCEPTION: A GROUNDING ELECTRODE SHALL NOT BE REQUIRED
 WHERE ONLY ONE BRANCH CIRCUIT, INCLUDING A MULTIWIRE
 BRANCH CIRCUIT, SUPPLIES THE BUILDING OR STRUCTURE AND
 THE BRANCH CIRCUIT INCLUDES AN EQUIPMENT GROUNDING
 CONDUCTOR FOR GROUNDING THE NONCURRENT-CARRYING PARTS
 OF ALL EQUIPMENT. FOR THE PURPOSES OF THIS SECTION, A
 MULTIWIRE BRANCH CIRCUIT SHALL BE CONSIDERED AS A
 SINGLE BRANCH CIRCUIT.
  
 2) SHOW LOCATION OF SERVICE IF SEPARATE FROM THE HOUSE
 YOU WILL NEED TO SEE THE ABOVE COMMENT FOR THE MAIN
 HOUSE ALSO.