| Plan Review Notes For Permit 20020104 |
| Permit Number |
20020104 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-11 09:52:39 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) IN LIEU OF REQUIRED REMOVAL OF SPRINKLERS CLEAR | | | SIGNAGE IN MULTIPLE LOCATIONS WILL BE REQUIRED STATING | | | THE SYSTEM IS INACTIVE. | | | | | | | | | 27.2* INACTIVE SPRINKLER SYSTEMS ABANDONED IN PLACE. | | | 27.2.1 WHERE ALL OR PART OF AN INACTIVE SPRINKLER | | | SYSTEM IS | | | ABANDONED IN PLACE, COMPONENTS INCLUDING SPRINKLERS, | | | HOSE | | | VALVES AND HOSES, AND ALARM DEVICES SHALL BE REMOVED. | | | 27.2.2 CONTROL VALVES ABANDONED IN PLACE SHALL HAVE THE | | | OPERATING | | | MECHANISMS REMOVED. | | | 27.2.3 SPRINKLER SYSTEM PIPING AND/OR VALVES ABANDONED | | | IN | | | PLACE SHALL BE UNIQUELY IDENTIFIED TO DIFFERENTIATE | | | THEM FROM | | | ACTIVE SYSTEM PIPING AND VALVES. | | | | | | PLEASE ENSURE COMPLIANCE AND COORDINATE SIGN LOCATION | | | WITH THE FIRE INSPECTOR. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|