| Plan Review Notes For Permit 20020083 |
| Permit Number |
20020083 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-03-12 11:45:42 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW | | | PLUMBING COMMENTS: DENIED | | | 1. PER WPB FBC 107.2.1, SHOW LOCATION OF EXISTING STACK | | | THAT WASHER DRYER IS TO BE CONNECTED TO. PROVIDE A | | | SANITARY RISER DIAGRAM SHOWING HOW KEYNOTE #7 ON PLAN | | | PAGE A2.2 WILL BE ACCOMPLISHED. IF THIS IS A SINGLE | | | PIPE STACK (WASTE STACK VENT AS DESCRIBED IN FBC PL | | | 913), IT SHALL NOT BE OFFSET. PLEASE REFER TO THE | | | PROVISIONS OF FBC PL 905, 909 AND 913 FOR GUIDANCE. | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 20020083 610 CLEMATIS ST | | | |
|