| 2020-02-11 13:50:55 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- ADDRESS OF PROJECT SHOWN ON ALL PLANS IS INCORRECT. |
| | THE CORRECT ADDRESS IS 610 CLEMATIS ST. NOT 601. REVISE |
| | AS REQUIRED. NOTE: COVER SHEET HAS 4 PLACES LISTING THE |
| | INCORRECT ADDRESS. PLEASE MAKE SURE ALL THE INFORMATION |
| | IS CORRECTED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- ONLY ONE SET OF PLANS WAS SIGNED AND SEALED BY THE |
| | ARCHITECT OF RECORD. THE OTHER COPY WAS NOT SIGNED AND |
| | SEALED. BOTH COPIES NEED TO BE SIGNED AND SEALED |
| | (ORIGINAL SEAL AND SIGNATURE) SEC. 107.1 CITY |
| | AMENDMENTS. CHAPTER 481 FLORIDA STATUTES. |
| | |
| | 3- INFORMATION ABOUT SPRINKLER HEADS IS NOT CLEAR. SEC. |
| | 107.2.1 CITY AMENDMENTS. KEY NOTE #8 ON THE DEMOLITION |
| | PLAN ON SHEET A2.1 CALLS FOR REMOVAL AND CAPPING OF |
| | EXISTING SIDEWALL SPRINKLER HEAD AND SUPPLY LINE. ON |
| | THE OTHER HAND, KEY NOTE #11ON THE NEW FLOOR PLAN ON |
| | SHEET A2.2 CALLS TO VERIFY IF EXISTING SPRINKLER HEAD |
| | WILL COVER THE NEW EXPOSED AREA. CLEARLY SPECIFY |
| | PROPOSED ALTERATION TO THE SPRINKLER SYSTEM. NOTE: |
| | SEPARATE PERMIT WILL BE REQUIRED. |
| | |
| | 4-FLOORING SOUND INSULATION MATERIAL FOR NEW TILE: |
| | |
| | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION |
| | (2017). |
| | |
| | B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| | REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017). |
| | |
| | C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| | REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017). |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING |
| | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE |
| | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED |
| | ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| | |
| | 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE |
| | VALUATION TO INCLUDE ALL COSTS OR PROVIDE COPY OF |
| | SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES. |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |