Plan Review Notes
Plan Review Notes For Permit 20020071
Permit Number 20020071
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-03-11 14:37:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE FENCED AREA APPEARS TO BE CLOSE OFF A PATH OF
 EGRESS TO A PUBLIC WAY FROM THE EXISTING WAREHOUSE.
  
 THE DOOR/GATE NEED TO BE IDENTIFIED AS AN EXIT AND
 PROVIDED WITH HARDWARE THAT DOES NOT REQUIRE SPECIAL
 KNOWLDGE OR EFFORT.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2.1.4.5 DOOR LEAF OPERATING FORCES.
 7.2.1.4.5.1 THE FORCES REQUIRED TO FULLY OPEN ANY DOOR
 LEAF
 MANUALLY IN A MEANS OF EGRESS SHALL NOT EXCEED 15 LBF
 (67 N) TO
 RELEASE THE LATCH, 30 LBF (133 N) TO SET THE LEAF IN
 MOTION, AND 15
 LBF (67 N) TO OPEN THE LEAF TO THE MINIMUM REQUIRED
 WIDTH, UNLESS
 OTHERWISE SPECIFIED AS FOLLOWS:
 (1) THE OPENING FORCES FOR INTERIOR SIDE-HINGED OR
 PIVOTEDSWINGING
 DOOR LEAVES WITHOUT CLOSERS SHALL NOT EXCEED 5 LBF
 (22 N).
 (2) THE OPENING FORCES FOR EXISTING DOOR LEAVES IN
 EXISTING
 BUILDINGS SHALL NOT EXCEED 50 LBF (222 N) APPLIED TO
 THE LATCH
 STILE.
 (3) THE OPENING FORCES FOR HORIZONTAL-SLIDING DOOR
 LEAVES IN
 DETENTION AND CORRECTIONAL OCCUPANCIES SHALL BE AS
 PROVIDED
 IN CHAPTERS 22 AND 23.
 (4) THE OPENING FORCES FOR POWER-OPERATED DOOR LEAVES
 SHALL BE
 AS PROVIDED IN 7.2.1.9.
 7.2.1.4.5.2 THE FORCES SPECIFIED IN 7.2.1.4.5 SHALL BE
 APPLIED TO THE
 LATCH STILE.
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 PLEASE REVIEW AND CORRECT/PROVIDE
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  