| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| | PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN |
| | HEADING ?SHUTTER INSTALLED? SHUTTERS ARE INSTALLED |
| | VERTICALLY AS PER SHEET 2 OF FL16893 R-5. PLEASE |
| | CORRECT COLUMN HEADING ?ANCHOR SPACING?; PROVIDE |
| | INFORMATION FROM PAGE 13 OF FL16893-R5. EXAMPLE: |
| | MAXIMUM A.S.D. DESIGN PRESSURE RATING (P.S.F.) +60.0, |
| | -60.0 OR LESS, MAXIMUM SPAN 72?; MOUNT TYPE C; ANCHOR |
| | TYPE A1 MAXIMUM ANCHOR SPACING IS 8?. SECOND REQUEST. |
| | |